Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

BOILERS AND HEAT PUMPS

WWP L A air-to-water outdoor heat pumps 20–60 kW, down to −25 °C, supply up to 70 °C

Air-to-water outdoor heat pumps of 20–60 kW, models WWP LA 20/30-A R and WWP LA 43/60-A R. At A7/W35 per DIN EN 14511 they give 11.6 kW (COP 5.40) and 22.67 kW (COP 5.11). They work at outdoor temperatures down to −25 °C, with a supply temperature up to 70 °C.

Models
WWP LA 20/30-A R; WWP LA 43/60-A R (range 20–60 kW)
Output (A7/W35, DIN EN 14511)
11.6 kW (COP 5.40); 22.67 kW (COP 5.11)
Energy efficiency class
A+++ (LT); A+++ / A++ (HT)
Outdoor temperature
operation down to −25 °C

Technical specifications

ModelsWWP LA 20/30-A R; WWP LA 43/60-A R (range 20–60 kW)
Output (A7/W35, DIN EN 14511)11.6 kW (COP 5.40); 22.67 kW (COP 5.11)
Energy efficiency classA+++ (LT); A+++ / A++ (HT)
Outdoor temperatureoperation down to −25 °C
Supply temperatureup to 70 °C
Modesheating, active cooling, DHW heating
Outdoor unit dimensions1517 × 1800 × 885 mm; 1764 × 1970 × 1000 mm
Designmodulated operation, electronic expansion valve, vibration isolation
CertificatesSG Ready, EHPA quality label

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The whole refrigeration circuit is placed in the outdoor unit, so little space is needed in the building. The unit dimensions are 1517 × 1800 × 885 mm for model 20/30 and 1764 × 1970 × 1000 mm for 43/60. The energy efficiency class is A+++ for low-temperature heating, and A+++ and A++ respectively for high-temperature heating. A supply temperature of up to 70 °C is suitable for existing buildings with radiator heating. Modulated operation removes cycling at full load, and the electronic expansion valve regulates the refrigerant flow. The manufacturer states that about five kilowatts of heat are obtained from one kilowatt of electricity. Active cooling is possible with suitable accessories. The pumps have SG Ready and the EHPA label, and online calculators are available for the seasonal coefficient and noise distances.

How to choose

First the heat output is compared. WWP LA 20/30-A R gives 11.6 kW and WWP LA 43/60-A R 22.67 kW at A7/W35, so the second model suits larger buildings, and its outdoor unit has larger dimensions. If there is no space for an outdoor unit, but groundwater is available or probes can be drilled, look at WWP W or WWP S.

Request a price and lead time

WWP L A air-to-water outdoor heat pumps 20–60 kW, down to −25 °C, supply up to 70 °C. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What are the output and COP of WWP LA?

11.6 kW at COP 5.40 for model 20/30-A R and 22.67 kW at COP 5.11 for 43/60-A R at A7/W35.

Down to what outdoor temperature does the pump work?

Down to −25 °C, and the supply temperature reaches 70 °C.

What are the dimensions of the outdoor unit?

1517 × 1800 × 885 mm for model 20/30 and 1764 × 1970 × 1000 mm for 43/60.

Can the pump be used for cooling?

Yes, with suitable accessories the pump works in active building cooling mode.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.