Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

EMERGENCY LIGHTING

ecoLD - self-contained LED emergency luminaire 50-350 lm

ecoLD is a basic series of self-contained LED emergency luminaires of 50-350 lm for escape routes, open areas and rooms with increased risk. It works in residential buildings, offices, shops, hotels and industrial sites, and when mains power is switched off the luminaire itself changes over to the built-in battery.

Luminous flux
50-350 lm
Autonomy
1; 1.5; 2; 3 h
Battery
NiCd; NiMH (self-test)
Mode
non-maintained / maintained, self-test

Technical specifications

Luminous flux50-350 lm
Autonomy1; 1.5; 2; 3 h
BatteryNiCd; NiMH (self-test)
Modenon-maintained / maintained, self-test
IP/IKIP43, IK04

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The range is the same as D-ecoLD. Non-maintained 1 h models, ecoLD 70, 90, 150, 220 and 320, have a flux of 70, 100, 160, 220 and 340 lm. For 1.5 h there are ecoLD 50-1.5 and 200-1.5 (50 and 240 lm), for 2 h 45-2 and 150-2 (50 and 200 lm), and for 3 h 50-3 and 130-3 (50 and 130 lm). Maintained P90, P240 and P320 work for 1 h at 100-340 lm, and P50-1.5, P200-1.5, P45-2, P150-2, P50-3 and P130-3 light also in normal mode. Self-test, index A, means a self-checking microprocessor and a Ni-MH battery, while standard models have Ni-Cd. Without a battery, L90, L240 and L380 are made for 90, 240 and 380 lm. Protection degree is IP43, impact resistance IK04. Pictograms for working as a sign measure 230×75 mm.

How to choose

The supply depends on the version. Non-maintained models require 230 V 50 Hz, maintained ones 220-230 V 50/60 Hz, and L models without a battery 110-240 V 50/60 Hz / 170-320 V DC or 24 V 50/60 Hz / 18-30 V DC for a central system. Non-maintained models are connected to the 50 TE remote controller. If an enclosure for damp rooms is needed, choose eco-esLD, and if a wider choice of recessing accessories is needed, D-ecoLD.

Request a price and lead time

ecoLD - self-contained LED emergency luminaire 50-350 lm. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What luminous flux do the 1 hour ecoLD models have?

ecoLD 70, 90, 150, 220 and 320 give 70, 100, 160, 220 and 340 lm respectively.

How does ecoLD with index L differ from the others?

Models L90, L240 and L380 have no battery and are powered from a central system, with a flux of 90, 240 and 380 lm.

Which standards does the ecoLD series meet?

The luminaires comply with EN 60598-2-22, EN 55015, EN 61000-3-2, EN 61547 and EN 62034, and also with directives 2014/35/EC, 2014/30/EC and RoHS 2011/65/EC. The halogen-free polycarbonate of the enclosure passed the glow wire test at 850 °C.

What batteries are fitted in ecoLD?

Ni-Cd in standard models and Ni-MH in versions with self-test.

What autonomy is available in ecoLD?

1, 1.5, 2 and 3 h, depending on the model, with a luminous flux from 50 to 350 lm.

Similar products

Emergency lighting

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.