CB / LPS - central battery emergency lighting system 300 W - 7.5 kVA
Country: · Model: CB / LPS
CB and LPS central battery units power the emergency lighting of a building from a common battery to EN 50171 in the range from 300 W to 7.5 kVA. CB is rated 580-7500 VA with 230 V AC and 24 V DC output, and wall-mounted LPS units give 24 V DC up to 300 W.
- CB
- 230 V AC / 24 V DC; 580-7500 VA; up to 20/40/60 output lines; VRLA batteries
- LPS
- 24 V DC, up to 300 W, 6 lines × 4 A, batteries 26/65 Ah, autonomy 0.5-8 h, Ethernet
- Standards
- EN 50171, EN 50172
Technical specifications
| CB | 230 V AC / 24 V DC; 580-7500 VA; up to 20/40/60 output lines; VRLA batteries |
|---|---|
| LPS | 24 V DC, up to 300 W, 6 lines × 4 A, batteries 26/65 Ah, autonomy 0.5-8 h, Ethernet |
| Standards | EN 50171, EN 50172 |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
Instead of a battery in each luminaire, a common battery stores the energy, which simplifies maintenance and monitoring. CB units work in switched (maintained-off) or continuous (maintained) mode. The power range covers 580, 800, 1250, 2500, 3300, 5000 and 7500 VA. There are up to 20 output lines in CB580, CB800 and CB1250, up to 40 in CB2500 and CB3300, and up to 60 in CB5000 and CB7500, and the autonomy time is set for each line separately. Sealed lead-acid VRLA batteries with accelerated charging are used. Per EN 50171 the unit has five potential-free contacts for fault, alarm and status, and maintenance per EN 50172 is managed by the DaisaTest system. The low-power LPS is mounted on a wall. The output is 24 V DC, maximum 300 W, six lines of 4 A with double terminals, each line maintained or non-maintained, with active short-circuit protection. The inputs are four digital ones, one analogue one for adjusting markers and a remote control input, and there are also four dry alarm contacts, a graphic display with a keypad and an Ethernet port.
How to choose
The unit type is determined by the load. For large installations take CB, selecting the power from 580 to 7500 VA and the number of lines 20, 40 or 60. For small sites and 24 V markers a wall-mounted LPS up to 300 W is enough. Between its two versions choose by capacity, LPS24-26 for 26 Ah in a 405×400×225 mm enclosure or LPS24-65 for 65 Ah in a 605×400×225 mm enclosure, and the operating time is programmed from 0.5 to 8 h.
Request a price and lead time
CB / LPS - central battery emergency lighting system 300 W - 7.5 kVA. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
What power ratings does the CB central battery range have?
580, 800, 1250, 2500, 3300, 5000 and 7500 VA, with 230 V AC or 24 V DC output.
How many output lines do CB units have?
Up to 20 in CB580, CB800 and CB1250, up to 40 in CB2500 and CB3300, and up to 60 in CB5000 and CB7500. Autonomy is set separately for each line.
What batteries and capacity do LPS units have?
VRLA batteries, LPS24-26 for 26 Ah and LPS24-65 for 65 Ah, and the operating time is programmed from 0.5 to 8 h.
What standards do CB units comply with?
They are built to EN 50171, and maintenance management per EN 50172 is carried out through the DaisaTest system.
Similar products
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.