DaisaTest - centralized emergency lighting monitoring system (TEV units)
Country: · Model: DaisaTest / TEV
DaisaTest is a centralized monitoring system that checks every emergency luminaire of an installation from one computer and schedules maintenance to the requirements of EN 50172. TCA series luminaires are connected by a bus to TEV-1000, TEV-500 or TEV-200 units, and these to the computer via RS232 or Ethernet.
- Controllers
- TEV-1000, TEV-500, TEV-200
- Communication
- bus to TCA luminaires; RS232 or Ethernet to PC
- Tests
- functional every 3-30 days, autonomy every 3-12 months
- Notifications
- e-mail, reports
Technical specifications
| Controllers | TEV-1000, TEV-500, TEV-200 |
|---|---|
| Communication | bus to TCA luminaires; RS232 or Ethernet to PC |
| Tests | functional every 3-30 days, autonomy every 3-12 months |
| Notifications | e-mail, reports |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
The system includes TCA luminaires with a self-test function and a bus interface, TEV control units and a control computer. The units work as communication nodes between the luminaires and the computer. The system continuously monitors the presence of mains power, communication with the luminaires, battery charge and short circuits. The functional test is performed by default every 30 days, and the interval is set from 3 to 30 days. The autonomy duration test runs every 3 months and is set from 3 to 12 months. Results are shown on the screen, and the system sends configurable notifications and reports by e-mail. CB central batteries also use DaisaTest for maintenance per EN 50172. The system is installed in hospitals, airports, shopping and office centres, hotels and universities, where manual checking of each luminaire is labour-intensive and documentation of tests is needed. The manufacturer has been designing emergency lighting since 1980.
How to choose
The connection to the computer is chosen for the existing infrastructure, RS232 or Ethernet. TEV units are made in three versions, TEV-200, TEV-500 and TEV-1000, but the capacity of each in terms of the number of luminaires is not stated on the system page, so it is clarified from the technical documentation. The luminaires in the installation must be of the TCA series, otherwise they cannot be connected to the bus.
Request a price and lead time
DaisaTest - centralized emergency lighting monitoring system (TEV units). We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
How often does DaisaTest perform the functional test of the luminaires?
By default every 30 days, and the interval is set from 3 to 30 days.
How often is the autonomy duration checked?
Every 3 months by default, and the interval is set from 3 to 12 months.
What control units are included in the system?
TEV-1000, TEV-500 and TEV-200. They serve as nodes between the TCA luminaires and the computer.
How is the system connected to the computer?
TEV units are connected to the computer via RS232 or Ethernet, and a bus cable runs to the luminaires.
What does the system monitor and how does it notify about faults?
Mains power, communication with the luminaires, battery charge and short circuits, and it sends notifications and reports by e-mail.