Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

INDUSTRIAL FANS

CJLINE, CKDR in-line extraction units 400 °C/2 h with continuous operation at 120 °C, up to ~22 400 m³/h

The CJLINE and CKDR in-line extraction units with a backward-curved impeller extract smoke at 400 °C/2 h (EN 12101-3) and run continuously with air up to +120 °C. The airflow in the tables reaches about 22 400 m³/h for CJLINE and 11 030 m³/h for CKDR. They are installed outside the fire zone, in technical rooms, in attics and above suspended ceilings.

Type
in-line extraction unit with a centrifugal impeller (backward-curved blades), installed outside the fire zone
CJLINE — fire resistance
400 °C/2 h and 300 °C/2 h, EN 12101-3, certificate 0370-CPR-0594
CJLINE — sizes / airflow
CJLINE-1131 … CJLINE-2880; up to ~22 400 m³/h
CJLINE — power supply
3~ 230/400 V 50 Hz (up to 4 kW), 400/690 V 50 Hz (above 4 kW); class F motors, IP55, 1 or 2 speeds

Technical specifications

Typein-line extraction unit with a centrifugal impeller (backward-curved blades), installed outside the fire zone
CJLINE — fire resistance400 °C/2 h and 300 °C/2 h, EN 12101-3, certificate 0370-CPR-0594
CJLINE — sizes / airflowCJLINE-1131 … CJLINE-2880; up to ~22 400 m³/h
CJLINE — power supply3~ 230/400 V 50 Hz (up to 4 kW), 400/690 V 50 Hz (above 4 kW); class F motors, IP55, 1 or 2 speeds
CKDR — fire resistanceF400, EN 12101-3, certificate 0370-CPR-2358
CKDR — sizes / power / airflow280…560; 0.37…3 kW; up to ~11 030 m³/h
CKDR — constructionlarge door with reversible hinges, 40 mm acoustic insulation, condensate drain, CM motor cover included
Continuous operationup to +120 °C (S1 −25…+120 °C)
Casinggalvanized steel
VersionsCJLINE/EC, CKDR/EC — EC motors; CKD — basic version

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

CJLINE has in-line coaxial inlet and outlet, so it is easily built into a straight section of duct. The casing is galvanized steel, certificate 0370-CPR-0594, duties S2 at 300 and 400 °C for 2 h each. The motors are class F on ball bearings, IP55, one or two speeds, with a supply of 230/400 V 50 Hz up to 4 kW and 400/690 V 50 Hz above 4 kW. Sizes range from CJLINE-1131 to CJLINE-2880, with 4-pole and 6-pole versions. CKDR (certificate 0370-CPR-2358) has a large door with reversible hinges, 40 mm acoustic insulation, a condensate drain and a CM motor cover included, and the casing can be mounted in different positions. Its motors are class F, IP55, with a single-phase 230 V or three-phase 230/400 V 50 Hz supply, and the ambient temperature is −25…+50 °C.

How to choose

For restaurant kitchens with hot and greasy air, as well as for corridors, car parks and retail areas, the unit is taken according to airflow. CKDR covers sizes 280–560 and a power of 0.37–3 kW, while CJLINE gives a higher airflow. If an EC motor is needed, there are CJLINE/EC and CKDR/EC with 40 mm acoustic insulation, and CKD is the basic version. On request, special windings for other voltages and two-speed motors are made.

Request a price and lead time

CJLINE, CKDR in-line extraction units 400 °C/2 h with continuous operation at 120 °C, up to ~22 400 m³/h. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

How does CJLINE differ from CKDR?

CJLINE has coaxial inlet and outlet for a straight section of duct. CKDR has a large service door and 40 mm acoustic insulation.

What fire resistance do CJLINE and CKDR have?

The EN 12101-3 requirement is 400 °C/2 h. CJLINE has certificate 0370-CPR-0594 and the 300 and 400 °C modes, and CKDR has certificate 0370-CPR-2358.

Up to what air temperature do the units run continuously?

Up to +120 °C, and in S1 duty from −25 to +120 °C.

What is the motor power of CKDR?

From 0.37 to 3 kW for sizes 280–560, with an airflow of up to 11 030 m³/h.

Is there a version with an EC motor?

Yes, CJLINE/EC and CKDR/EC. CKD is the basic version.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.