CHT, CVT roof centrifugal smoke extraction fans 400 °C/2 h, up to ~24 700 m³/h

The CHT and CVT roof centrifugal fans extract smoke at 400 °C for 2 h to EN 12101-3 (certificate 0370-CPR-1892), with a maximum airflow in the tables of about 24 700 m³/h. CHT discharges air horizontally and CVT vertically. They are installed on the roof outside the fire zone.

Type
roof centrifugal smoke extraction fan, installed outside the fire zone
Fire resistance
400 °C/2 h to EN 12101-3, certificate 0370-CPR-1892
Air outlet
CHT — horizontal; CVT — vertical
Sizes
200…630 (per datasheet)

Technical specifications

Typeroof centrifugal smoke extraction fan, installed outside the fire zone
Fire resistance400 °C/2 h to EN 12101-3, certificate 0370-CPR-1892
Air outletCHT — horizontal; CVT — vertical
Sizes200…630 (per datasheet)
Maximum airflowup to ~24 700 m³/h
Handled air temperature (continuous)−25…+120 °C
Impellerbackward-curved blades, galvanized steel
Motorclass F, IP55 (single-phase — IP54), 1 or 2 speeds
Power supply1~ 230 V 50 Hz or 3~ 230/400 V 50 Hz
Ambient temperature−25…+50 °C
Materialsbase — galvanized steel, cowl — aluminum, bird screen
VersionsCHT/EC, CVT/EC — EC motors; CHT/ATEX, CVT/ATEX; ATEX cat. 3 on request

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The base is made of galvanized sheet steel, the impeller has backward-curved galvanized steel blades, and on top there is a bird screen and an aluminum rain cowl. In continuous operation the fan handles air from −25 to +120 °C, so it is also used to extract warm air from kitchens and process rooms. The motors have insulation class F, ball bearings, IP55 protection (IP54 for single-phase) and one or two speeds. The supply is single-phase 230 V 50 Hz or three-phase 230/400 V 50 Hz, and the ambient temperature is from −25 to +50 °C. Sizes range from 200 to 630, with 4-pole and 6-pole versions. The fan works both in daily extraction mode and in emergency smoke extraction mode. On request, special windings for other voltages and ATEX category 3 certification are made.

How to choose

The discharge direction is set by the layout of the shaft leading to the roof, horizontal for CHT and vertical for CVT. The CHT/EC and CVT/EC versions have EC motors and F400 certification, so output in daily mode is regulated without an external frequency converter. CHT/ATEX and CVT/ATEX are intended for explosive atmospheres of category 2. If the fan has to operate directly in the fire zone, look at the axial roof fans HTMF and THT/ROOF. The models are available in QuickFan and as BIM models.

Request a price and lead time

CHT, CVT roof centrifugal smoke extraction fans 400 °C/2 h, up to ~24 700 m³/h. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What fire resistance do the CHT and CVT fans have?

400 °C for 2 h to EN 12101-3, certificate 0370-CPR-1892. They are installed outside the fire zone.

How does CHT differ from CVT?

By the direction of air discharge. CHT has a horizontal outlet and CVT a vertical one.

What air temperature can be handled in daily mode?

In continuous mode from −25 to +120 °C. For this reason the fan is also suitable for warm air from kitchens.

What is the power supply of these fans?

Single-phase 230 V 50 Hz or three-phase 230/400 V 50 Hz, depending on the model. The motors are IP55, and single-phase ones IP54.

Can output be regulated without a frequency converter?

Yes, in the CHT/EC and CVT/EC versions with EC motors and F400 certification.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.