grid | power V L low-maintenance OPzS cells
Country: Germany · Model: grid | power V L (OPzS)
Flooded low-maintenance OPzS 2 V cells of up to 3500 Ah and 6 and 12 V blocks with tubular plates. They are designed for long discharge from 1 to over 10 hours in power engineering, at substations, in telecommunications and emergency lighting.
- Technology
- flooded lead-acid with liquid electrolyte, tubular plates
- Design
- 2 V cells (up to 3500 Ah), OPzS blocks of 6 and 12 V
- Options
- AquaGen recombination plugs
- Standards
- DIN 40736-1, IEC 60896-11
Technical specifications
| Technology | flooded lead-acid with liquid electrolyte, tubular plates |
|---|---|
| Design | 2 V cells (up to 3500 Ah), OPzS blocks of 6 and 12 V |
| Options | AquaGen recombination plugs |
| Standards | DIN 40736-1, IEC 60896-11 |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
Liquid electrolyte and tubular positive plates give the durability of a stationary battery that stands for years in float mode on a DC switchboard. The flooded design requires a ventilated room and periodic topping up with distilled water, but the condition of each cell can be seen from the electrolyte level and density. Optional AquaGen recombination plugs return part of the gas to water, so topping up is needed less often and less hydrogen is released. A capacity of up to 3500 Ah in a single 2 V cell covers the load of large substations and power plants without parallel strings. The cells are made to DIN 40736-1, and the tests meet IEC 60896-11.
How to choose
The discharge duration from 1 to over 10 hours and the required capacity determine the cell size. For small automation batteries, OPzS blocks of 6 and 12 V are more convenient. AquaGen plugs are worth ordering together with the cells if staff are rarely present on site. When there is no separate battery room, switch to sealed series, for example AGM grid | power VR M with 2 V cells up to 1000 Ah.
Request a price and lead time
grid | power V L low-maintenance OPzS cells. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
What is the maximum capacity of grid | power V L OPzS cells?
The 2 V cells are made with a capacity of up to 3500 Ah. For smaller batteries there are OPzS blocks of 6 and 12 V.
What discharge time are OPzS V L cells designed for?
For long discharge from 1 to over 10 hours. For discharges lasting minutes, thin-plate series are a better fit.
What are AquaGen plugs for?
AquaGen recombination plugs return gases as water, so the topping-up interval grows and less hydrogen is released. The option is available for 2 V cells and for 6 and 12 V blocks.
Which standards do OPzS V L cells meet?
The cells are made to DIN 40736-1 and meet IEC 60896-11 for flooded lead-acid batteries.