LHT — high-temperature AGM batteries

The LHT series is designed to operate at 35 °C, that is, in containers and cabinets without air conditioning. It includes 12 V AGM monoblocks of 100–200 Ah and 2 V cells of 200–1000 Ah for telecom and emergency systems.

Technology
AGM VRLA
Voltage
2 V (200–1000 Ah), 12 V (100–200 Ah)
Service life
up to 10 years (12 V) and 15 years (2 V) at 35 °C
Reference temperature
35 °C

Technical specifications

TechnologyAGM VRLA
Voltage2 V (200–1000 Ah), 12 V (100–200 Ah)
Service lifeup to 10 years (12 V) and 15 years (2 V) at 35 °C
Reference temperature35 °C
CaseABS+PC, UL94-V0

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The service life here is stated specifically at 35 °C, so it can be compared directly with the real conditions of an uncooled site. The 12 V monoblocks last up to 10 years, the 2 V cells up to 15 years. Dropping air conditioning reduces the power consumption of the base station, and the series was created for exactly this scenario. The valve-regulated VRLA design returns gas into the reaction, so topping up with water is not needed. The case made of an ABS+PC blend has class UL94-V0 and does not support combustion, which matters for cabinets next to power equipment. The two-volt cells are assembled into batteries for long backup time, while monoblocks suit compact cabinets and emergency power systems.

How to choose

The deciding factors are the site temperature and the required backup time. For 100–200 Ah take 12 V monoblocks; for larger banks up to 1000 Ah build a string from 2 V cells, which also last longer. If the equipment is in an air-conditioned room, the front-terminal gel LPFG will give a longer life.

Request a price and lead time

LHT — high-temperature AGM batteries. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

At what temperature can LHT batteries be operated?

The reference temperature of the series is 35 °C, and the service life is calculated for it. That is why the batteries are installed in cabinets and containers without air conditioning.

How long does an LHT AGM battery last at 35 °C?

Up to 10 years for 12 V monoblocks and up to 15 years for 2 V cells.

What is the maximum capacity of 2 V LHT cells?

The two-volt cells are made for 200–1000 Ah, the 12 V monoblocks for 100–200 Ah.

What fire safety class does the LHT case have?

The ABS+PC case has flammability class UL94-V0, that is, it self-extinguishes once the flame is removed.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.