PowerSafe VM / GFM and SuperSafe TM / GFM / T-MJ — high-capacity modular AGM systems
Country: USA · Model: PowerSafe VM / GFM, SuperSafe TM / GFM / T-MJ
PowerSafe VM / GFM and SuperSafe TM / GFM / T-MJ modular AGM systems are built from 2–12 V blocks rated 200–5,000 Ah (C10). They target large telecom, utility and UPS batteries where fast installation counts.
- Technology
- VRLA-AGM
- Voltage
- 2–12 V
- Capacity
- 200–5,000 Ah (C10)
- Construction
- modules with integrated rack system
Technical specifications
| Technology | VRLA-AGM |
|---|---|
| Voltage | 2–12 V |
| Capacity | 200–5,000 Ah (C10) |
| Construction | modules with integrated rack system |
| Customs codes (for reference) | |
| HS code | 8507.20 |
| UKTZED code (Ukraine) | 8507208090 |
| CN code (EU) | 85072080 |
Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.
Description
Each module arrives with an integrated rack system, so the battery goes together like a kit without separate rack assembly and leveling. Modules are stacked in tiers, and inter-cell links and terminals stay on one serviceable side. VRLA-AGM is sealed, needs no watering and puts milder demands on the room than flooded batteries. Capacity up to 5,000 Ah in a single string of 2 V cells covers substation DC supply and backup for large telecom nodes without parallel strings. Fewer parallel strings mean simpler balancing and monitoring. The lower end of the range at 200 Ah makes the system usable at mid-size sites too.
How to choose
Capacity is chosen from load current and backup time at the C10 rate, and the 200–5,000 Ah range usually fits in one string. If a data center UPS needs high 15-minute power, look at flooded DataSafe DX at 240–5,448 W/cell or sealed DataSafe XE. Small telecom cabinets do not need modular systems, and Genesis TD at 50–202 Ah is enough there.
Request a price and lead time
PowerSafe VM / GFM and SuperSafe TM / GFM / T-MJ — high-capacity modular AGM systems. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
What capacity do PowerSafe VM and SuperSafe TM modular systems have?
The line covers 200–5,000 Ah at the C10 rate, with blocks of 2–12 V.
What does the integrated rack system offer?
Modules form the battery without a separate rack, which shortens installation time and simplifies leveling.
Where are PowerSafe GFM and SuperSafe T-MJ systems used?
In telecom, power utilities and UPS installations that need large capacity and fast battery installation.
Do PowerSafe VM AGM modules need watering?
No, these are sealed VRLA-AGM batteries. Maintenance comes down to checking voltages, temperature and connection torque.
Why build a large battery from 2 V cells?
Large 2 V cells deliver the required backup in a single series string, with no parallel strings and no balancing issues between them.