Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

LIFEPO4 LITHIUM BATTERIES

grid | power FNC-VR low-maintenance NiCd batteries with gas recombination

FNC nickel-cadmium batteries with a low-pressure valve and gas recombination of up to 90 %, with a water topping-up interval of up to 20 years at 20 °C. They are intended for UPS with autonomy from an hour to several days.

Technology
nickel-cadmium FNC with low-pressure valve, recombination up to 90 %
Water topping-up interval
up to 20 years at 20 °C
Operating temperature
−50…+60 °C (per brochure)
Service life
up to 25 years

Technical specifications

Technologynickel-cadmium FNC with low-pressure valve, recombination up to 90 %
Water topping-up intervalup to 20 years at 20 °C
Operating temperature−50…+60 °C (per brochure)
Service lifeup to 25 years
StandardsIEC/EN 60623

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The low-pressure valve keeps gases inside the cell, where up to 90 % of oxygen and hydrogen becomes water again, so electrolyte loss is minimal. At 20 °C the topping-up interval reaches 20 years and the service life is up to 25 years, so over the whole life the battery is serviced very rarely. At higher temperature evaporation increases and the interval shortens. The manufacturer's brochure states an operating range of −50…+60 °C, which makes it possible to install the battery in unheated cabinets at remote sites. FNC fiber-structure electrodes keep the resistance of the NiCd battery to deep discharges and mechanical loads. The design meets IEC/EN 60623.

How to choose

Between FNC-VR and the open FNC the choice is made by maintenance capability. If the site is visited rarely, the recombination version with a topping-up interval of up to 20 years is more convenient. The capacity and number of cells are determined by the required autonomy, from an hour to several days, and the UPS bus voltage. For rooms with a stable climate a gel or AGM series is enough, for example grid | power VR M with a service life of up to 15 years.

Request a price and lead time

grid | power FNC-VR low-maintenance NiCd batteries with gas recombination. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

How often should water be added to FNC-VR batteries?

The topping-up interval is up to 20 years at 20 °C. At higher temperature the electrolyte level should be checked more often.

What is the degree of gas recombination in FNC-VR?

Up to 90 %. The rest of the gas leaves through the low-pressure valve, so the room still needs ventilation.

In what temperature range does FNC-VR work?

According to the manufacturer's brochure from −50 to +60 °C. For projects at extreme temperatures, check the data for the specific cell type.

What is the service life of FNC-VR batteries?

Up to 25 years, and the batteries meet the IEC/EN 60623 standard.

What UPS autonomy can be obtained with FNC-VR?

The series is designed for autonomy from an hour to several days, and recombination of up to 90 % makes it suitable for remote sites.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.