PowerSafe / SuperSafe OPzV — 2 V gel cells, 215–3,170 Ah
Country: USA · Model: PowerSafe OPzV, SuperSafe OPzV
OPzV gel cells rated 2 V with tubular positive plates and 215–3,170 Ah at the C10 rate. They are meant for telecom, power and medical sites where the battery has to stand for years with almost no service.
- Technology
- VRLA, gel electrolyte, tubular plates
- Voltage
- 2 V
- Capacity
- 215–3,170 Ah (C10)
- Format
- DIN, capacity above the DIN rating
Technical specifications
| Technology | VRLA, gel electrolyte, tubular plates |
|---|---|
| Voltage | 2 V |
| Capacity | 215–3,170 Ah (C10) |
| Format | DIN, capacity above the DIN rating |
| Customs codes (for reference) | |
| HS code | 8507.20 |
| UKTZED code (Ukraine) | 8507208090 |
| CN code (EU) | 85072080 |
Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.
Description
The electrolyte is gelled and does not stratify, so the cell runs without agitation or specific gravity checks. The VRLA valve design keeps gas inside, no water is added, and periodic inspection plus voltage checks are enough. A tubular plate holds the active mass and tolerates deep discharge better than a flat plate, which matters in substations with long emergency loads. The cells follow the DIN format, and each size carries more capacity than the DIN rating. In practice the same rack footprint holds more ampere-hours. The battery is built in series from single 2 V cells up to the required bus voltage.
How to choose
The cell is chosen by C10 capacity within 215–3,170 Ah and by the cell count per bus. If watering is acceptable and a ventilated battery room exists, the vented OPzS series offers the same DIN format. For small 12 V gel systems Genesis FPG at 33–250 Ah fits, and for nickel-cadmium chemistry in hard frost GAZ covers −50…+70 °C.
Request a price and lead time
PowerSafe / SuperSafe OPzV — 2 V gel cells, 215–3,170 Ah. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
How does OPzV differ from OPzS?
OPzV has gel electrolyte and a valve regulated case, so no water is added. The 2 V cells offer 215–3,170 Ah at C10.
How many OPzV cells make a 48 V bus?
Each cell is rated 2 V, so a 48 V bus takes a series string of twenty-four cells.
What does capacity above the DIN rating mean for OPzV?
The cell dimensions follow DIN, but it holds more ampere-hours than the standard value, up to 3,170 Ah in the largest size.
Where are 2 V OPzV gel cells used?
The maker lists telecom, power utilities and medical facilities, and the 215–3,170 Ah range covers both telecom nodes and substation DC boards.
Similar products
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.