grid | power V X (GroE) 2 V Planté cells
Country: Germany · Model: grid | power V X (GroE)
Planté 2 V cells of approx. 75–2600 Ah with very low internal resistance and a design life of up to 25 years. They are installed at power plants and in switchgear, where the battery must deliver high current in a short time.
- Technology
- flooded lead-acid, pure-lead Planté plates
- Voltage
- 2 V
- Capacity
- approx. 75–2600 Ah
- Design life
- up to 25 years
Technical specifications
| Technology | flooded lead-acid, pure-lead Planté plates |
|---|---|
| Voltage | 2 V |
| Capacity | approx. 75–2600 Ah |
| Design life | up to 25 years |
| Standards | DIN 40738, IEC 60896-11 |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
Planté plates are made of pure lead, and the active mass forms directly on the developed plate surface. Hence the low internal resistance, small voltage drop at the start of discharge and the ability to power breaker coils, starting and emergency loads. This design ages slowly, so the design life reaches 25 years. The cells are flooded, so a ventilated room and electrolyte control are needed. The range from 75 to 2600 Ah covers both small substations and large plants. The design meets DIN 40738 and IEC 60896-11.
How to choose
The cell capacity is selected by the current of the heaviest short load and the duration of the emergency mode, not simply by the nominal Ah. The number of 2 V cells in the string determines the voltage of the DC switchboard. If the room has no ventilation, consider the sealed grid | power VR M series with 2 V cells up to 1000 Ah. For UPS with discharge in minutes on 12 V blocks, grid | power VR X at 57–166 Ah is suitable.
Request a price and lead time
grid | power V X (GroE) 2 V Planté cells. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
How do GroE Planté cells differ from OPzS?
GroE has pure-lead Planté plates with very low internal resistance, so it is stronger on short high-current discharges. The service life reaches 25 years.
What is the capacity of grid | power V X (GroE) cells?
Approx. 75–2600 Ah at a cell voltage of 2 V.
What is the service life of GroE Planté cells?
The design life is up to 25 years. Planté plates age slowly, so such a battery is installed at sites with a long life cycle.
Which standards do GroE cells meet?
DIN 40738 and IEC 60896-11 for flooded stationary lead-acid 2 V cells.
Similar products
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.