Genesis EP / XE — 12 V high-power TPPL batteries
Country: USA · Model: Genesis EP / XE
Genesis EP and XE batteries use TPPL thin pure lead plates and deliver up to 4,189 W per cell over 15 minutes from a 12 V block. The compact units go into UPS systems, renewable plants, hybrid electric vehicles and special-purpose equipment, and they are safe enough for offices and hospitals.
- Technology
- TPPL, VRLA
- Voltage
- 12 V
- Capacity
- EP 13–72 Ah (C10, Europe), up to 200 Ah (USA); XE 13 Ah
- Power
- EP 348–4,189 W/cell; XE 330–2,482 W/cell (15 min)
Technical specifications
| Technology | TPPL, VRLA |
|---|---|
| Voltage | 12 V |
| Capacity | EP 13–72 Ah (C10, Europe), up to 200 Ah (USA); XE 13 Ah |
| Power | EP 348–4,189 W/cell; XE 330–2,482 W/cell (15 min) |
| Application | UPS, renewables, hybrid electric vehicles, special-purpose equipment |
| Customs codes (for reference) | |
| HS code | 8507.20 |
| UKTZED code (Ukraine) | 8507208090 |
| CN code (EU) | 85072080 |
Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.
Description
Thin plates give more active surface per unit of volume, hence high power density in a small footprint. EP capacity in the European catalog is 13–72 Ah (C10), and the US range includes blocks up to 200 Ah. For XE the data give 13 Ah. At a 15-minute discharge EP covers 348–4,189 W/cell and XE 330–2,482 W/cell. The VRLA case is sealed and the electrolyte immobilized, so the blocks can sit near people in office server rooms and medical premises. Pure lead corrodes more slowly than alloys, so the battery holds its rated figures longer on float charge.
How to choose
For short UPS discharges select by watts per cell, and for renewables and vehicles by C10 capacity. If you need blocks above 72 Ah, check the US EP range up to 200 Ah or move to DataSafe XE with 205–1,040 Ah. Projects with no power density demands can use Genesis NP AGM blocks.
Request a price and lead time
Genesis EP / XE — 12 V high-power TPPL batteries. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
How much power do Genesis EP batteries deliver?
At a 15-minute discharge EP gives 348–4,189 W per cell depending on size. For XE the range is 330–2,482 W/cell.
What capacity does Genesis EP have in Europe and the USA?
The European EP range covers 13–72 Ah (C10), while US blocks go up to 200 Ah. Check which range your supplier carries before ordering.
Can Genesis EP be installed in an office or hospital?
Yes, the maker states these sealed TPPL blocks are safe for offices and hospitals. Room ventilation is still calculated to VRLA rules.
What does TPPL mean in Genesis batteries?
TPPL stands for thin plate pure lead. This construction raises power density and slows grid corrosion.
What is Genesis XE used for?
XE, rated 13 Ah, serves the same UPS, renewable, hybrid vehicle and special equipment uses as EP, where high current from a small case is needed.