SWITCHGEAR AND PACKAGE SUBSTATIONS
Backup — backup and off-grid power units
Country: Germany · Model: Backup
Backup power units come in 1P, 3P Kit, Hybrid X and Off-Grid versions, with load current up to 63 A on the Hybrid X version, while the Backup 100 and 300 commercial cabinets are rated 100 and 300 kW. During a grid outage the unit disconnects the site and transfers loads to the inverter and battery.
- Versions
- Backup 1P, Backup 3P Kit, Backup for Hybrid X, Backup Off-Grid for Sunny Island X/Storage XL
- Load current
- up to 63 A (Hybrid X)
- Consumption
- < 1 W standby (1P/3P), < 4 W in backup (Hybrid X)
- Functions
- automatic transfer, black start
Technical specifications
| Versions | Backup 1P, Backup 3P Kit, Backup for Hybrid X, Backup Off-Grid for Sunny Island X/Storage XL |
|---|---|
| Load current | up to 63 A (Hybrid X) |
| Consumption | < 1 W standby (1P/3P), < 4 W in backup (Hybrid X) |
| Functions | automatic transfer, black start |
| More from the manufacturer’s documentation | |
| Backup for Hybrid X models | BU-STPH-3P63K / 4P63K / 3P63B / 4P63B (3- or 4-pole disconnection; box or DIN-rail kit) |
| Parallel operation (Hybrid X) | up to 3 hybrid inverters |
| Backup for Hybrid X: enclosure | 506 × 260 × 236 mm, 6.6 kg, IP65, −40 °C to +45 °C |
| Backup 1P: compatible inverters | SBSE3.6-50 / SBSE4.0-50 / SBSE5.0-50 / SBSE6.0-50 |
| Backup 1P: power | 7,300 W; 11,040 W < 100 ms; 9,200 W < 30 s |
| Backup 1P: grid | 230 V, 50 / 60 Hz; grid-side pre-fuse up to 63 A |
| Backup 1P: switching time | adjustable 0–600 s (default 5 s), actual ≈ 100 ms |
| Backup 1P: enclosure | 506 × 260 × 236 mm, 6.16 kg, IP65, −40 °C to +55 °C, up to 3,000 m |
| Backup 100 / 300: power | 100 kW (AC-Box 2) / 300 kW (AC-Box 6); up to 2 / 6 Sunny Island X or Sunny Tripower Storage X inverters |
| Backup 100 / 300: loads | 135 kW, 195 A, NH1 (200 A) / 300 kW, 435 A, NH3 (500 A) |
| Backup 100 / 300: grid | 230 / 400 V, 300–440 V (L–L), 50 / 60 Hz; TN-S, TN-C-S |
| Backup 100 / 300: enclosure | 1,200 × 1,600 × 435 mm, 200 kg, IP55 / 1,200 × 2,000 × 800 mm, 400 kg, IP54; −20 °C to +40 °C |
| Backup 100 / 300: equipment | integrated Data Manager M (EDMM-20), 8-port LAN switch, generator management |
| Standards (Backup 100 / 300) | EN IEC 61439-1/-2, VDE-AR 2510-2 |
| Warranty | 2 years (Backup 1P, Backup for Hybrid X); 5 years (Backup 100 / 300) |
| Customs codes (for reference) | |
| HS code | 8537.10 |
| UKTZED code (Ukraine) | 8537109890 |
| CN code (EU) | 85371098 |
Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.
Description
The units come factory-assembled and just connect to the switchboard on site. Transfer to backup is automatic, and black start is supported. In standby the 1P and 3P versions draw under 1 W, and the Hybrid X version draws under 4 W in backup. Backup 1P for the single-phase SBSE3.6-50 to SBSE6.0-50 carries 7,300 W continuously, 9,200 W for up to 30 s and 11,040 W for up to 100 ms, and actually switches over in about 100 ms. It sits behind a pre-fuse of up to 63 A, in a 6.16 kg IP65 enclosure rated −40 °C to +55 °C. Backup for Hybrid X comes as a box or a DIN-rail kit with 3- or 4-pole disconnection and serves up to 3 hybrid inverters. The Off-Grid version is meant for systems with Sunny Island X and Storage XL. The Backup 100 and 300 cabinets carry a built-in Data Manager M, a LAN switch and genset management.
How to choose
The inverter decides the version. A single-phase Sunny Boy Smart Energy takes Backup 1P or the 3P Kit, a Sunny Tripower Hybrid X takes the unit of the same name, and the 4-pole version is for sites where the neutral must also be broken when islanding. For a business, size by load. Backup 100 with AC-Box 2 feeds up to 135 kW at 195 A on an NH1 (200 A) fuse and Backup 300 with AC-Box 6 up to 300 kW at 435 A on NH3 (500 A).
Request a price and lead time
Backup — backup and off-grid power units. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
What load current does Backup for Hybrid X handle?
Up to 63 A, with up to 3 hybrid inverters connected.
How much does Backup 1P draw in standby?
Under 1 W, and the Hybrid X version draws under 4 W in backup.
Does Backup support black start?
Yes, the units transfer to backup automatically and can start the system without the grid.
How fast does Backup 1P switch a home to the battery?
In practice about 100 ms. The delay is adjustable within 0–600 s, 5 s by default.
REQUEST
Need a price, lead time or replacement?