Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

VOLTAGE STABILIZERS

R120 – R630 — analog automatic voltage regulators (AVR) for synchronous generators

The analog automatic voltage regulators R120–R630 control the excitation of synchronous generators with a current from 3.2 A in the R220 to 15 A in the R630. They work with SHUNT, AREP, AREP+ and PMG systems on TAL and LSA generators, and are used as spare parts and for upgrading generator sets, marine and industrial power plants.

Models
R120, R150, R180 (TAL series); R220, R250, R450, R610, R630 (LSA series)
Excitation current
3.2 A (R220) – 15 A (R630); R120 — 4 A / 6 A 30 s
Excitation systems
SHUNT, AREP, AREP+, PMG, SHUNT + booster
Regulation accuracy
±0.5 % (R120 — ±1 %, R150 — ±0.8 %)

Technical specifications

ModelsR120, R150, R180 (TAL series); R220, R250, R450, R610, R630 (LSA series)
Excitation current3.2 A (R220) – 15 A (R630); R120 — 4 A / 6 A 30 s
Excitation systemsSHUNT, AREP, AREP+, PMG, SHUNT + booster
Regulation accuracy±0.5 % (R120 — ±1 %, R150 — ±0.8 %)
Frequency range10–100 Hz / 20–100 Hz
FunctionsU/f limiting, overexcitation and short circuit current limiting; droop and parallel operation; load acceptance module LAM (R250, R450)
R610 / R630three-phase sensing, cos φ / kVAr modes, voltage matching, stator current limiting
DiscontinuedR438, R449 — replacement with SWITCH2D350 / SWITCH2D550 kits

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

Three models are intended for the TAL series. The R120 on SHUNT gives 4 A (6 A for 30 s) with ±1 % accuracy in the 20–100 Hz range, has U/f limiting with k = 1.2, protection against loss of sensing voltage and overexcitation limiting. The R150 delivers 6 A (8 A for 30 s) with ±0.8 % accuracy and adds droop, while the R180 for AREP+ and PMG gives 6 A (9 A for 5 s), ±0.5 % and supports a remote potentiometer. In the LSA series the smallest R220 with 3.2 A and 10–100 Hz comes in three-phase and single-phase versions, and for single-phase machines at 60 Hz there is the R221. The 5 A R250 is complemented by the load acceptance module LAM. The 6 A R450 works with SHUNT, PMG or AREP, limits overexcitation and short circuit current, has droop and LAM; the R450M variant is supplied with Mate-N-Lok connectors and the R450T with a three-phase sensing module. The R726 module adds cos φ regulation to it, and the R729 also adds kVAr with a 4–20 mA signal.

How to choose

The model is determined by the generator series, the excitation system and the current. The 10 A R610 for SHUNT, AREP, PMG or SHUNT with booster has three-phase sensing and droop, with cos φ and kVAr modes optional. The 15 A R630 adds manual and tracking modes, voltage matching before synchronisation, grid power factor regulation and stator current limiting, so it suits operation in parallel with the grid. In place of the discontinued R438 and R449 the manufacturer recommends the digital D350 and D550 with ±0.25 % accuracy.

Request a price and lead time

R120 – R630 — analog automatic voltage regulators (AVR) for synchronous generators. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What can replace the discontinued R438 or R449 regulator?

For the R438 there is the SWITCH2D350 kit with the digital D350 regulator, and for the R449 the SWITCH2D550 kit with the D550.

What accuracy do the analog AVRs R120–R630 give?

Most models hold voltage with ±0.5 % accuracy, the R120 holds ±1 %, and the R150 holds ±0.8 %.

Which regulators are suitable for parallel operation of generators?

Droop for load sharing is available on the R150, R180, R450 and R610. The R630 has voltage matching before synchronisation and grid power factor regulation.

Is there a regulator for a single-phase 60 Hz generator?

Yes, the R221 is made for single-phase 60 Hz machines, and the basic R220 exists in three-phase and single-phase versions.

Similar products

Voltage stabilizers

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.