Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

VOLTAGE STABILIZERS

CR power conditioner (stabilizer) 1–2000 kVA

The CR power conditioner combines voltage stabilization with suppression of mains interference and is available at 1–75 kVA single-phase and 3–2000 kVA three-phase. The unit is designed for professional use, including laboratories, server rooms and industrial automation.

Power
1-phase 1–75 kVA (CR-21…CR-34/1); 3-phase 3–2000 kVA (CR-31…CR-54)
Efficiency at full load
95%
Response time
2 ms
Principle
buck-boost transformer with triacs and microprocessor control

Technical specifications

Power1-phase 1–75 kVA (CR-21…CR-34/1); 3-phase 3–2000 kVA (CR-31…CR-54)
Efficiency at full load95%
Response time2 ms
Principlebuck-boost transformer with triacs and microprocessor control
Protectionsoverload, min./max. mains and output voltage
Protection degreeIP20

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

Regulation is performed by a buck-boost transformer whose winding is switched by triacs under microprocessor control, with a response time of 2 ms. Suppression of impulse and high-frequency interference from the mains is added to this, so CR is appropriate where a stable voltage alone is not enough. Efficiency at full load is 95%, slightly lower than for the SE stabilizer because of the additional stages. The electronics monitor overload, as well as the minimum and maximum mains and output voltage. Single-phase models are designated CR-21…CR-34/1, three-phase CR-31…CR-54. The IP20 enclosure is installed in an electrical or server room.

How to choose

The boundary between SE and CR is set by mains quality: if the problem is only voltage deviations, SE with 98% efficiency is enough, while with interference from frequency converters and welding posts nearby CR is better. Power is taken with a margin over the total load; the single-phase range ends at 75 kVA, beyond that only three-phase units up to 2000 kVA. For one device up to 5 kVA there is the compact SH, and the conditioner does not protect against a complete mains loss, for which an online UPS is needed.

Request a price and lead time

CR power conditioner (stabilizer) 1–2000 kVA. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

How does a power conditioner differ from a voltage stabilizer?

A stabilizer only levels the voltage, while the CR conditioner also suppresses mains interference. Both units are built on a buck-boost transformer with triacs.

What is the power of CR power conditioners?

Single-phase CR-21…CR-34/1 have 1–75 kVA, three-phase CR-31…CR-54 up to 2000 kVA.

What protections does the CR conditioner have?

Overload protection and monitoring of the minimum and maximum voltage of both the mains and the output.

How fast does the CR power conditioner respond?

The response time is 2 ms, and efficiency at full load is 95%.

Similar products

Voltage stabilizers

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.