SVS — single-phase 230 V stabilizers 0.5–5 kVA

SVS single-phase solid-state 230 V stabilizers are made in ratings from 0.5 kVA (4 A) to 5 kVA (20 A). They feed refrigeration equipment, air conditioners, computers and satellite receivers where the mains voltage is unstable.

Current / power
4 A (0.5 kVA) – 20 A (5 kVA)
Output accuracy
230 V ±6 %
Cut-off
at input < 142 V or > 295 V
Protection
against surges, spikes on restoration, basic lightning protection

Technical specifications

Current / power4 A (0.5 kVA) – 20 A (5 kVA)
Output accuracy230 V ±6 %
Cut-offat input < 142 V or > 295 V
Protectionagainst surges, spikes on restoration, basic lightning protection
FunctionsAVS, start delay, TimeSave
Technologysolid-state

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The output holds 230 V with an accuracy of ±6 %. When the input voltage falls below 142 V or rises above 295 V, the stabilizer switches the load off, that is, the built-in AVS function works as a voltage relay. After the mains returns, power is supplied with a start delay, and TimeSave does not add an unnecessary pause if the mains was absent longer than the delay time. The circuit has no moving parts, no brushes and no servo motor, so it reacts quickly and does not wear out. Against surges, spikes on restoration and lightning the unit gives basic-level protection; it does not replace a full SPD at the entry. The top model SVS20 is designed for fixed connection to the wiring, the smaller ones plug into a socket.

How to choose

The rating is selected by the starting power, which for a refrigerator or air conditioner is several times the running power. For a PC and a TV 0.5 kVA is enough; for an air conditioner or a group of appliances take the 5 kVA model. If the mains regularly sags below 142 V, it is better to look at the SVS…-22E with a 110–305 V input, and for protecting a whole house at the wall-mounted SVS WM.

Request a price and lead time

SVS — single-phase 230 V stabilizers 0.5–5 kVA. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

At what voltage does the SVS stabilizer switch the load off?

Cut-off occurs if the input voltage is below 142 V or above 295 V. After the mains normalizes, power returns with a start delay.

What output accuracy does the single-phase SVS stabilizer give?

The output voltage is 230 V with ±6 % accuracy, which is sufficient for household and office equipment.

Which SVS model is connected permanently?

The 20 A SVS20 is designed for fixed connection to the electrical wiring. The smaller models from 4 A (0.5 kVA) work from a socket.

Does the SVS stabilizer protect against lightning overvoltages?

It has basic lightning protection and suppresses surges and spikes when the mains is restored. At high-risk sites a separate SPD is installed in front of it.

Similar products

Voltage stabilizers

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.