EMS1000 / EMS1000 PRO / LC100 — controllers for energy storage and solar plants
Country: China · Model: EMS1000 / EMS1000 PRO / LC100
The EMS1000, EMS1000 PRO and LC100 controllers collect data from inverters and storage units, distribute power and convert communication protocols. The first two are installed on commercial BESS and solar plants, and the LC100 controls ORI stations up to 7.5 MW / 30 MWh.
- Application
- commercial storage systems and solar plants
- Functions
- parallel control, fault recording, automatic inverter address search (PRO)
- LC100
- BESS ORI controller: up to 36 PCS (7.5 MW / 30 MWh), Modbus TCP, IEC 104, IEC 61850, GOOSE, 12–24 V DC supply, 15 W
Technical specifications
| Application | commercial storage systems and solar plants |
|---|---|
| Functions | parallel control, fault recording, automatic inverter address search (PRO) |
| LC100 | BESS ORI controller: up to 36 PCS (7.5 MW / 30 MWh), Modbus TCP, IEC 104, IEC 61850, GOOSE, 12–24 V DC supply, 15 W |
| Customs codes (for reference) | |
| HS code | 9032.89 |
| UKTZED code (Ukraine) | 9032890000 |
| CN code (EU) | 90328900 |
Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.
Description
The EMS1000 coordinates parallel operation of several inverters or PCS and records fault events, which simplifies fault analysis on site. The EMS1000 PRO version adds automatic search of inverter addresses, so during commissioning there is no need to enter each device manually on the communication bus. The LC100 is designed for ORI systems and supports up to 36 PCS in one station. For exchange with dispatch systems the controller has Modbus TCP, IEC 104 and IEC 61850 with GOOSE messages, so the station is integrated into substation SCADA over standard power-industry protocols. The LC100 is powered by 12–24 V DC and consumes 15 W, so it is supplied from the cabinet's operating DC circuit or from a separate power supply. All three devices work as the upper level of the station, which issues power setpoints for inverters and storage units.
How to choose
The choice is determined by the type and size of the site. For a commercial storage system or solar plant with several inverters the EMS1000 is suitable, and with a large number of devices the PRO with automatic address search is more convenient. The LC100 is needed only for grid ORI stations, where up to 36 PCS operate and exchange with the dispatcher over IEC 61850 or IEC 104 is required.
Request a price and lead time
EMS1000 / EMS1000 PRO / LC100 — controllers for energy storage and solar plants. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
Which protocols does the LC100 controller support?
The LC100 works with Modbus TCP, IEC 104, IEC 61850 and GOOSE messages. This set is enough for connection to substation SCADA.
How many PCS can the LC100 control?
Up to 36 PCS in an ORI station, which corresponds to a power of 7.5 MW and a capacity of 30 MWh.
How does the EMS1000 PRO differ from the EMS1000?
The PRO adds automatic search of inverter addresses. Parallel control and fault recording are present in both versions.
What power supply does the LC100 controller need?
The controller is powered by 12–24 V DC and consumes 15 W, so the cabinet's operating DC circuit is suitable.
What sites is the EMS1000 intended for?
The EMS1000 is installed on commercial storage systems and solar plants where several inverters must be run as one system.