Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

CHARGE CONTROLLERS AND EMS

Advanced Application Temperature Controller UT75A

The UT75A is a digital temperature controller with a large color 14-segment LCD and navigation keys. Indication accuracy is ±0.1% of full scale. Ladder sequence logic comes as standard, and the shallow case saves space on the instrument panel.

[Example of ladder instruction]
[Example of ladder programming]
Item
UT75A
Number
1 (std) 2 (max)
Indication accuracy
±0.1% of F.S.

Technical specifications

[Example of ladder instruction][Example of ladder programming]
ItemUT75A
Number1 (std) 2 (max)
Indication accuracy±0.1% of F.S.
AlgorithmON/OFF, PID (continuous, time-proportional), heating/cooling, position-proportional
TypeRS-485, Ethernet, PROFIBUS-DP, CC-Link, DeviceNet
FunctionPV high, PV low, deviation high, etc.
Power consumptionMax 18 VA
MassMax 0.5 kg
TCK, J, T, B, S, R, N, E, L, U, W PL-2, PR20-40, W97Re3-W75Re25
RTDJPt100, Pt100
DC voltage0.4 to 2.0 V, 1.0 to 5.0 V, 0.0 to 2.0 V, 0 to 10 V, -10 to 20 mV, 0 to 100 mV
DC current4 to 20 mA, 0 to 20 mA

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The controller accepts thermocouples K, J, T, B, S, R, N, E, L, U and two tungsten-rhenium types, Pt100 and JPt100 RTDs, and standard signals of 4 to 20 mA, 0 to 20 mA and voltage up to 10 V. Available algorithms are ON/OFF, PID with continuous or time-proportional output, heating/cooling and position-proportional valve control. Alarms are generated by functions such as PV high, PV low and deviation high. Communication runs over RS-485, Ethernet, PROFIBUS-DP, CC-Link or DeviceNet, so the unit fits into open plant networks. Power consumption is at most 18 VA and mass is at most 0.5 kg.

How to choose

The main points when selecting the UT75A are the list of input signals and the network type. Check that your sensor appears among the thermocouple, RTD, current and voltage inputs. For PROFIBUS-DP, CC-Link or DeviceNet pick the matching communication variant, whereas Ethernet and RS-485 need no extra steps. If ladder logic and the extended inputs are not needed, look at the simpler mid-level controllers of the same line.

Request a price and lead time

Advanced Application Temperature Controller UT75A. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

Which sensors can be connected to the UT75A?

Thermocouples K, J, T, B, S, R, N, E, L, U, Pt100 and JPt100 RTDs, 4 to 20 mA and 0 to 20 mA signals and voltage up to 10 V are supported.

Which networks does the UT75A support?

RS-485, Ethernet, PROFIBUS-DP, CC-Link and DeviceNet are available. This lets you connect the controller to a PLC or SCADA without separate converters.

What is the indication accuracy of the UT75A?

Indication accuracy is ±0.1% of full scale. The actual measurement error also depends on the sensor type you select.

What control algorithms does the UT75A offer?

These are ON/OFF, PID with continuous or time-proportional output, heating/cooling and position-proportional control. The last one is used for motorized valves.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.