Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

DC-DC CONVERTERS AND BATTERY CHARGERS

IDC — isolated DC-DC converter 12/24/48 V, 100–360 W

IDC isolated DC-DC converters come in 100, 200 and 360 W versions with 9–18, 18–36 or 36–72 V DC input. Load current is up to 30 A, input-to-output isolation > 400 V RMS, efficiency up to 85%. They power 12 V equipment from a 24 V vehicle system or a 48 V station battery when the two circuits must not share a negative.

Power
100, 200 and 360 W; IDC-30
Input
9–18 V, 18–36 V or 36–72 V DC
Output
12.5 V and others (series A–D)
Current
up to 30 A

Technical specifications

Power100, 200 and 360 W; IDC-30
Input9–18 V, 18–36 V or 36–72 V DC
Output12.5 V and others (series A–D)
Currentup to 30 A
Isolation> 400 V RMS
Efficiencyup to 85%
IDC-360iMversion with 20 A battery charging function
Customs codes (for reference)
HS code8504.40
UKTZED code (Ukraine)8504409000
CN code (EU)85044095

Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.

Description

Galvanic isolation matters on special-purpose vehicles, trucks, buses, marine vessels and telecom systems, where input and output must not share a common point. At a telecom site with a positive-grounded 48 V battery, or on a boat with an isolated DC system, the converter breaks the current path between circuits and removes the ground loops that carry noise into radio gear. The 9–18, 18–36 and 36–72 V input ranges cover 12, 24 and 48 V systems including sag and charging voltage. Output is 12.5 V and other voltages across series A–D. The IDC-360iM version also charges a battery at 20 A. The maker also lists IDC-30 among the power ratings.

How to choose

First pick the input range to match the source voltage, then the power by the load, and at 12.5 V the 360 W model gives close to 30 A. If the load needs a buffer battery on the output, take the IDC-360iM with 20 A charging. When isolation is not needed and both systems share a negative, the non-isolated SDC at 5–60 A with 20–35 V input is simpler and cheaper. For charging a service battery from the smart alternator of a EURO 5/6 vehicle, the Elogic EL at 30–50 A fits.

Request a price and lead time

IDC — isolated DC-DC converter 12/24/48 V, 100–360 W. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What isolation voltage does the IDC have?

Input-to-output isolation is > 400 V RMS.

Which input ranges does the IDC cover?

9–18, 18–36 or 36–72 V DC, matching 12, 24 and 48 V systems.

Can the IDC charge a battery?

Yes, the IDC-360iM version charges a battery at 20 A.

How do I run a 12 V radio from a 48 V telecom battery?

Use an IDC with 36–72 V input and 12.5 V output. The > 400 V RMS isolation keeps the radio negative apart from the grounded positive of the station battery.

How efficient are IDC converters?

Up to 85%, and the rest turns into heat, so a 360 W unit needs airflow around it.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.