Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

ELECTRIC MOTORS

STAMFORD S4 — low-voltage synchronous generator 210–560 kVA

The low-voltage brushless generator S4 for sets of 210–560 kVA. In the Dedicated version it gives 260–450 kVA at 50 Hz and 325–563 kVA at 60 Hz (class H, 125/40 °C), with a voltage of 380–690 V and 1500/1800 rpm. For 450 kVA a new core length has appeared with an optimized power density.

Output 50 Hz
260–450 kVA (class H, 400 V)
Output 60 Hz
325–563 kVA (480 V)
Range
210–560 kVA
Voltage
380–690 V

Technical specifications

Output 50 Hz260–450 kVA (class H, 400 V)
Output 60 Hz325–563 kVA (480 V)
Range210–560 kVA
Voltage380–690 V
Number of poles4
Winding pitch2/3
Excitationself-excited; option — PMG
AVRAS440 (standard); DECS150, DM110, MX321, MX341, VITA 05
Insulationclass H
ProtectionIP23
SAE adaptors0, 0.5, 1, 2
CoolingCoreCooling

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The CoreCooling system is patented; it improves the thermal condition of the windings and gives more power in the same frame size. The winding is wire, with a 2/3 pitch, class H insulation and IP23 protection; as standard it is self-excited with the analog AS440 and two-phase voltage sensing. Optionally fitted are a PMG sub-exciter, the regulators MX321, MX341, DECS150 and DM110, the digital VITA 05, three-phase sensing and the UL version. The designations are S4L1D (Dedicated), S4L1S (Special) and S4L1M (Marine). Adaptor feet allow a changeover between the S4 and S5 without modifying the frame, with SAE adaptors 0, 0.5, 1, 2. Factory options include an anti-condensation heater, a quadrature droop kit, RTD sensors, thermistors and a rotating diode failure detector.

How to choose

The Dedicated version is narrower than the full range of 210–560 kVA, so the limit is chosen by mains frequency, that is 260–450 kVA at 50 Hz or 325–563 kVA at 60 Hz. If less is needed, see the UC27 (75–312 kVA); if more, the S5 (450–937 kVA). For ships there is the S4L1M, and flexible feet make it easier to replace a generator of another make.

Request a price and lead time

STAMFORD S4 — low-voltage synchronous generator 210–560 kVA. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What output does the S4 generator have at 50 and 60 Hz?

260–450 kVA at 50 Hz and 400 V and 325–563 kVA at 60 Hz and 480 V. The full range of the series is 210–560 kVA.

What is CoreCooling in the S4?

A patented air cooling scheme. It improves the thermal condition of the windings, so more power is obtained in the same frame size.

What do the designations S4L1D, S4L1S and S4L1M mean?

D means Dedicated with increased power density, S means Special, and M means Marine, that is the marine version.

Which voltage regulators can be fitted to the S4?

The standard AS440, and optionally the DECS150, DM110, MX321, MX341 and the digital VITA 05.

Can the S4 be changed over to the S5 without modifying the frame?

Yes, adaptor feet are provided for this. SAE adaptors 0, 0.5, 1, 2, and single-bearing and two-bearing versions.

Similar products

Electric motors

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.