Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

ELECTRIC MOTORS

STAMFORD S9 LV — low-voltage synchronous generator 2430–4400 kVA

The largest low-voltage frame size of the S-Range, the S9 LV (S9L1D), gives 2430–4400 kVA at 50 Hz and 2132–4220 kVA at 60 Hz depending on voltage. In the base version at 400 V and 50 Hz it gives up to 4250 kVA in class H (125/40 °C). The voltages are 380–415 V, with 1500/1800 rpm and four poles.

Output 50 Hz
2430–4400 kVA (various voltages); up to 4250 kVA at 400 V
Output 60 Hz
2132–4220 kVA
Voltage
380–415 V (LV version), up to 690 V
Number of poles
4

Technical specifications

Output 50 Hz2430–4400 kVA (various voltages); up to 4250 kVA at 400 V
Output 60 Hz2132–4220 kVA
Voltage380–415 V (LV version), up to 690 V
Number of poles4
ExcitationPMG
AVRDM110 (standard), DECS150
Regulation accuracy±0.25 %
Insulationclass H
ProtectionIP23
SAE adaptor0 or no adaptor
StandardsIEC 60034, BS5000-3, ISO 8528-3, VDE 0530, NEMA MG1-32, CSA C22.2-100, AS 60034; ISO 9001

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The generator is brushless with PMG excitation; the digital regulator DM110 is fitted as standard and the DECS150 is optional. The voltage regulation accuracy is ±0.25 % at 4 % engine governor droop. The insulation is class H (data for class F, 105/40 °C, are also available), the protection is IP23 and the cooling is CoreCooling. The no-load voltage waveform distortion is less than 1.5 %, and the telephone influence factor TIF is < 50. The data conform to IEC 60034, BS5000-3, ISO 8528-3, VDE 0530, NEMA MG1-32, CSA C22.2-100 and AS 60034, radio interference suppression is to BS EN 61000-6-2 and 61000-6-4, and the quality system is BS EN ISO 9001. Options include an SAE 0 adaptor, an RTD on each bearing, controlled short circuit and anti-condensation heaters.

How to choose

For 380–415 V this is the most powerful low-voltage frame size of the S-Range, and lower outputs are covered by the S5 and S6 (up to 1695 kVA at 60 Hz). The medium- and high-voltage versions S9M1D and S9H1D are covered in a separate item. All data are given for four poles at 1500/1800 rpm.

Request a price and lead time

STAMFORD S9 LV — low-voltage synchronous generator 2430–4400 kVA. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What output does the S9 LV have at 50 and 60 Hz?

2430–4400 kVA at 50 Hz and 2132–4220 kVA at 60 Hz depending on voltage. At 400 V and 50 Hz, up to 4250 kVA.

Which voltage regulator is fitted in the S9 LV?

The digital DM110 as standard, and the DECS150 as an option. The regulation accuracy is ±0.25 % at 4 % engine governor droop.

Which standards are the S9 data confirmed to?

IEC 60034, BS5000-3, ISO 8528-3, VDE 0530, NEMA MG1-32, CSA C22.2-100 and AS 60034. Production operates to BS EN ISO 9001.

What is the voltage waveform distortion in the S9 LV?

Less than 1.5 % at no load, and the telephone influence factor TIF is less than 50.

Are the medium-voltage S9 models included in this item?

No, the S9M1D and S9H1D versions are covered in a separate item. Only the S9L1D for 380–415 V is included here.

Similar products

Electric motors

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.