Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

ELECTRICAL SAFETY EQUIPMENT AND PPE

Copper-bonded earthing rods 14.2–18.2 mm and clamps TGT / GTR / TRP / PTR

Copper-bonded earthing rods of 14.2, 14.6 and 18.2 mm diameter and 1.5 or 2.0 m length, together with the clamps TGT, GTR, TRP and PTR, form the earthing system of substations, poles and buildings. The steel core withstands driving into the ground, and the 100 or 300 µm copper coating protects against corrosion.

Rods
calibrated steel, electrolytic copper bonding 100 or 300 µm
Diameter × length
14.2 mm × 1.5/2.0 m; 18.2 mm × 2.0 m (100 µm); 14.6 mm × 2.0 m (300 µm)
Rod clamps
TGT142, TGT142 RF (reinforced), TGT142C, TGT142C-A2 (Ø18.6 mm), GTR — brass
Conductor clamps
TRP (parallel), GDC (wall-mounted), CDCC-50 (50 mm² cross piece), TMV-8

Technical specifications

Rodscalibrated steel, electrolytic copper bonding 100 or 300 µm
Diameter × length14.2 mm × 1.5/2.0 m; 18.2 mm × 2.0 m (100 µm); 14.6 mm × 2.0 m (300 µm)
Rod clampsTGT142, TGT142 RF (reinforced), TGT142C, TGT142C-A2 (Ø18.6 mm), GTR — brass
Conductor clampsTRP (parallel), GDC (wall-mounted), CDCC-50 (50 mm² cross piece), TMV-8
Coating of copper partstinning 15 µm
PTR linkpolyester, cable up to 70 mm²
StandardsUNE-EN IEC 62561-1:2023, UNE 202006; AENOR certificate

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The rods are made of calibrated steel with an electrolytic copper coating. The sizes 14.2 mm × 1.5 and 2.0 m and 18.2 mm × 2.0 m have a 100 µm coating, and 14.6 mm × 2.0 m has 300 µm. They comply with UNE-EN IEC 62561-1:2023 and UNE 202006 and are AENOR certified. The conductor is fixed to the rod with brass clamps: TGT142 with a galvanized steel yoke for 14.2 and 14.6 mm rods, the reinforced TGT142 RF, the closed TGT142C, TGT142C-A2 for 18.6 mm and GTR with stainless screws. The parallel clamp TRP is intended for overhead line conductors. Tinned copper parts with 15 µm tinning, GDC for wall mounting, CDCC-50 for crossing 50 mm² cables and TMV-8 for an 8 mm copper rod with an M8×35 screw, are installed inside substations. The PTR polyester link is a disconnectable point for measuring earth resistance and accepts cable up to 70 mm². For branches there are also the crimped CRC and the screw-type TR/TRT.

How to choose

The rod size is chosen by the soil and the length of the loop. Copper of 100 µm is on the 14.2 and 18.2 mm rods, while the 14.6 mm rod with a 300 µm coating gives a thicker copper layer. The clamp is selected by rod diameter, TGT142 for 14.2 and 14.6 mm. Loop branches are made with CRC or TR/TRT, while GDC, CDCC-50 and TMV-8 remain for loops inside substations.

Request a price and lead time

Copper-bonded earthing rods 14.2–18.2 mm and clamps TGT / GTR / TRP / PTR. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What diameters and lengths do the copper-bonded rods have?

14.2 mm in lengths of 1.5 and 2.0 m, 18.2 mm in a length of 2.0 m, and 14.6 mm in a length of 2.0 m.

What is the thickness of the copper coating on the rods?

100 µm for the 14.2 and 18.2 mm rods and 300 µm for the 14.6 mm one. The steel core gives strength when driving.

Which standards do the rods comply with?

UNE-EN IEC 62561-1:2023 and UNE 202006, with AENOR certification.

What is the PTR link for?

It is a disconnectable point for measuring earth resistance, and it accepts cable of up to 70 mm² cross-section.

Which clamps suit a 14.2 mm rod?

TGT142 with a galvanized steel yoke, the reinforced TGT142 RF, the closed TGT142C and GTR with stainless screws.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.