ECBT / ELBT portable earths for panels and 0.4 kV overhead lines, and for electric vehicles

The ECBT and ELBT low-voltage portable earths per IEC 61230 short-circuit the phases with the neutral and connect them to earth in panels, cabinets, transformer substations and on 0.4 kV overhead lines, with copper cables in PVC insulation of 16 to 120 mm². If a section is switched on by mistake or voltage comes back through back-feed, the protection will trip and no dangerous potential will appear at the workplace. Separate kits are intended for workshops servicing electric and hybrid vehicles.

Standard
IEC 61230
ECBT panel kits
SHUNT3/4, PTA3/4, NH, ID, ID-NH, GNF, 4MPUE, 4MPUL, 4MPUHL, MPUBTH
Cable cross-section
25–120 mm² (Cu, PVC insulation) depending on the model
Clamps
SHUNT (SHCD/SHPL), PTA (under screw heads on busbars), MPUC, MPUL with insulated handle, MPUBT/H for busbars

Technical specifications

StandardIEC 61230
ECBT panel kitsSHUNT3/4, PTA3/4, NH, ID, ID-NH, GNF, 4MPUE, 4MPUL, 4MPUHL, MPUBTH
Cable cross-section25–120 mm² (Cu, PVC insulation) depending on the model
ClampsSHUNT (SHCD/SHPL), PTA (under screw heads on busbars), MPUC, MPUL with insulated handle, MPUBT/H for busbars
Earthing knivesNH000–NH4 for NH fuses, installed with an insulating stick (M10 thread)
0.4 kV overhead lines ELBT-PAT/CC4 spring clamps PEBT on 70 cm sticks, wire Ø 3–18 mm, Cu 16 mm²
Shunt kit KS-2FB-05016flexible 50 mm² cable with bayonet connectors
Vehicle kits PAT-2/F-600, PAT-TT38Lprotection against induced voltage and static during servicing of electric and hybrid cars and trucks

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

Every kit includes insulated clamps, copper cables and a terminal for connecting to the earthing device. The ECBT-SHUNT4 has four insulated SHUNT clamps of type SHCD or SHPL for bare wires and busbars, which short-circuit the three phases and earth the neutral, while the ECBT-SHUNT3 manages with three clamps. The PTA clamps of the ECBT-PTA3/PTA4 kits are fixed under screw heads on busbars. In the ECBT-NH, ECBT-ID, ECBT-ID-NH and ECBT-GNF the NH earthing knives are inserted in place of NH fuses with an insulating stick with an M10 thread, the earthing is applied directly on the fuse base, and the fuses themselves are removed and fitted without risk. The ECBT-MPUBTH is intended for busbars of LV panels, and the three-phase PATC-3MPUL for busbars of LV/MV transformer substation cells. The KS-2FB-05016 shunt kit with a flexible 50 mm² cable on bayonet connectors is used for temporary links and measurements.

How to choose

The kit is chosen by what the earthing will be connected to. Bare wires and busbars are covered by the ECBT-SHUNT4 or ECBT-SHUNT3, screw heads by the ECBT-PTA, and where NH fuses are installed, earthing knives are handier. When the expected short-circuit current is high, switch to the ECBT-4MPUL or ECBT-4MPUHL. The insulating sticks BM, BMTS, BMAI, BMAE and BSC have the M10 head for installing the knives. For medium-voltage overhead lines there is the PATL series with automatic clamps, and for earthing an overhead line by one worker the ERLAIN kit.

Request a price and lead time

ECBT / ELBT portable earths for panels and 0.4 kV overhead lines, and for electric vehicles. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What is the cable length in the ECBT-SHUNT4 kit?

The phase cables with a cross-section of 25 mm² are 1.2 m long, the neutral cable 1.5 m. The SHUNT clamps are suitable for bare wires and busbars.

Which kit is used to earth a 0.4 kV overhead line?

The ELBT-PAT/CC is intended for 0.4 kV overhead lines. Four spring PEBT clamps on 70 cm sticks are applied to wires of Ø 3–18 mm, and the connecting cables have a cross-section of 16 mm².

What is the largest cable cross-section in ECBT panel kits?

The reinforced ECBT-4MPUL and ECBT-4MPUHL with MPUL clamps with a built-in insulated handle are made with cables of 70, 95 and 120 mm² for higher short-circuit currents.

Why is earthing needed when repairing an electric vehicle?

The PAT-2/F-600 and PAT-TT38L kits protect mechanics from induced voltage and static electricity when servicing electric and hybrid cars and trucks.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.