BATTERY ENERGY STORAGE SYSTEMS (BESS)
OMNI — all-in-one BESS cabinets and containers 260 kWh – 2.2 MWh
Country: China · Model: OMNI
The OMNI energy storage system ships pre-assembled with its PCS, from the L260-OMNI cabinet with 260 kWh to the 20-foot A1000, A2000 and L2200-OMNI containers with 1–2.2 MWh. It connects to a 400 V network at factories, shopping centers, PV plants and substations.
- Models
- L260-OMNI (260 kWh), A1000-OMNI (1,034.88 kWh), A2000-OMNI (2,069.76 kWh), L2200-OMNI (2,231 kWh), L520-OMNI, L3300-OMNI
- Cells
- LFP
- A2000-OMNI
- 20 ft container 6058 × 2438 × 2896 mm, 28 t, 2 PCS of 500 kW each, 400 V, air cooling, IP55
- DC voltage
- 638–781 V (A1000/A2000), 702–936 V (L260), 716.8–921.6 V (L2200)
Technical specifications
| Models | L260-OMNI (260 kWh), A1000-OMNI (1,034.88 kWh), A2000-OMNI (2,069.76 kWh), L2200-OMNI (2,231 kWh), L520-OMNI, L3300-OMNI |
|---|---|
| Cells | LFP |
| A2000-OMNI | 20 ft container 6058 × 2438 × 2896 mm, 28 t, 2 PCS of 500 kW each, 400 V, air cooling, IP55 |
| DC voltage | 638–781 V (A1000/A2000), 702–936 V (L260), 716.8–921.6 V (L2200) |
| Cooling | air (A series), liquid (L series) |
| Cycle life | > 7,000 cycles (A2000), 8,500 (L260) |
| Standards | IEC 62619, IEC 62040-1, VDE 2510-50, UL 1973, UL 9540A, EN 50549-1, G99 |
| Customs codes (for reference) | |
| HS code | 8507.60 |
| UKTZED code (Ukraine) | 8507600000 |
| CN code (EU) | 85076000 |
Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.
Description
The flagship A2000-OMNI in a 6058 × 2438 × 2896 mm container weighs 28 t and stores 2,069.76 kWh, with two 500 kW PCS units at 400 V inside, which works out to about 0.5C. The A-series battery is air-cooled in an IP55 enclosure. L-series models, including the L260 and the 2,231 kWh L2200, use liquid cooling, which keeps cell temperature more even and extends service life. Cycle life differs as well, over 7,000 for the A2000 and 8,500 for the L260. DC bus voltage is 638–781 V on the A1000/A2000, 702–936 V on the L260 and 716.8–921.6 V on the L2200. The set complies with IEC 62619, IEC 62040-1, VDE 2510-50, UL 1973, UL 9540A, EN 50549-1 and the British G99.
How to choose
First define the energy, then the power-to-capacity ratio. For a commercial site up to 260 kWh the L260-OMNI cabinet is enough, while for megawatt-hours the choice is between the A1000-OMNI with 1,034.88 kWh and the A2000-OMNI. If a PCS is already in place or a 1500 V architecture is needed, the battery-only L5000-BAT or PyOcean are used. There are no parameters for the L520-OMNI and L3300-OMNI in our data.
Request a price and lead time
OMNI — all-in-one BESS cabinets and containers 260 kWh – 2.2 MWh. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
What PCS power does the A2000-OMNI have?
The container houses 2 PCS units of 500 kW each with a 400 V output. With 2,069.76 kWh of capacity that is a two-hour discharge profile.
How does the OMNI A series differ from the L series?
The A series is air-cooled, the L series liquid-cooled. The L260 is rated for 8,500 cycles against more than 7,000 for the A2000.
How much does the A2000-OMNI container weigh?
It weighs 28 t at 6058 × 2438 × 2896 mm, a standard 20-foot container. It needs a foundation and a crane of matching capacity.
Is OMNI approved for grid connection in the UK?
The standards list includes the British G99 as well as EN 50549-1 for European networks. Specific models for a project are confirmed with the manufacturer.
Similar products
REQUEST
Need a price, lead time or replacement?