BATTERY ENERGY STORAGE SYSTEMS (BESS)

The manufacturer scalecube i3 grid-scale BESS block 7.25 MWh / 4.6 MVA

The scalecube i3 grid-scale storage system is built from BESU blocks of 7,250 kWh usable energy and 4,600 kVA, each with 2 battery containers and 1 PCS station. A block connects to a 10–36 kV, 50 Hz grid through its own 4.6 MVA oil-immersed transformer and MV switchgear. Such plants are built for electricity trading, balancing power and co-location.

Cells
LFP prismatic 306 Ah
Container energy
4,073.47 kWh nominal
BESU block
2 battery containers + 1 PCS, 7,250 kWh usable (AC MV), 4,600 kVA
Grid voltage
10–36 kV, 50 Hz

Technical specifications

CellsLFP prismatic 306 Ah
Container energy4,073.47 kWh nominal
BESU block2 battery containers + 1 PCS, 7,250 kWh usable (AC MV), 4,600 kVA
Grid voltage10–36 kV, 50 Hz
Inverter4,600 kVA, 690 V, DC 1003–1500 V, efficiency up to 99.2%
Modesgrid-following, grid-forming (virtual synchronous machine)
Container20 ft, IP55, liquid cooling, ~36 t
Operating temperature−25…+45 °C
More from the manufacturer’s documentation
Container dimensions (H × W × D)2.896 × 6.058 × 2.438 m
BESU layout area (W × D)17.5 × 16.2 m (283.5 m²), minimum for service
Scaling stepsFixed steps from 8.1 MWh / 4.6 MVA
Max. charge/discharge power0.5P
Self-discharge≤ 3.5% per month (DC decoupled)
Sound power levelBattery container 85 ± 3 dB(A); PCS 91 ± 3 dB(A), approx. 85 dB(A) with sound reduction
Humidity< 95%, non-condensing
Installation altitudeUp to 2 km above sea level
Corrosion protection classC5
Design life≥ 15 years (depending on load profile)
Product/performance warrantyUp to 15 years
Grid frequency range47–53 Hz
Communication interfacesModbus TCP/IP; with IAU: Modbus RTU, IEC 60870-5-104, IEC 60870-5-101, digital/analog I/O card
ApplicationsEnergy trading, multi-market optimization incl. balancing power and co-location, peak shaving, self-consumption optimization, external EMS control, backup power
PCS unit: dimensions (H × W × D), weight2.896 × 6.058 × 2.438 m, < 18 t
PCS IP ratingIP23D (control rooms) / IP54 (inverter electronics)
Inverter max. AC current3.85 kA
Power factor (cos φ)0 (ind.) … 1 … 0 (cap.)
Max. THD< 3% at rated power
TransformerOil type, 4,600 kVA, Dy11, KNAN cooling, impedance 6%, tap changer ±2 × 2.5%, oil containment tray with filter
Transformer lossesNo-load 4.14 kW, max. 38.7 kW (Eco Design, tier 2)
MV switchgearCable – cable – circuit breaker, definite-time overcurrent protection, short-circuit withstand 20 kA, 1 s
ColorContainer RAL 7042; PCS RAL 9016 / RAL 7004
ZEREZ certificates (VDE-AR-N 4110 / 4120 / 4130)ZE-7ZWF-D8MS
Battery standardsEN 61000-6-2, EN 61000-6-4, EN 62619, IEC 62477, IEC 62933-5-2, UN 38.3, UL 1973, NFPA 855, UL 9540A
Inverter standardsCE, IEC/EN 62109-1/-2, VDE-AR-N 4110/4120/4130, IEC 61000-6-2, EN 55011, TOR A, TOR B
Transformer and switchgear standardsEN 50588-1, IEC 60076; IEC 62271-200, IEC 62271-202
Customs codes (for reference)
HS code8507.60
UKTZED code (Ukraine)8507600000
CN code (EU)85076000

Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.

Description

The 20 ft container uses prismatic 306 Ah LFP cells and stores 4,073.47 kWh nominal, with liquid cooling, IP55 protection and a weight of about 36 t. The 4,600 kVA inverter outputs 690 V, takes 1003–1500 V DC and reaches up to 99.2% efficiency. Besides grid-following mode it runs grid-forming, behaving as a virtual synchronous machine. The Dy11 KNAN transformer has 6% impedance and a ±2 × 2.5% tap changer, with an oil containment tray and filter under the tank. The MV breaker panel withstands 20 kA short-circuit current for 1 s. THD stays below 3% at rated power. The equipment runs from −25 to +45 °C at altitudes up to 2 km.

How to choose

The system grows in fixed steps from 8.1 MWh / 4.6 MVA, and one BESU with service aisles needs a 17.5 × 16.2 m plot (283.5 m²). If the same 4,600 kVA has to carry more energy, look at scalecube i4 with 530 Ah cells and 10.378 MWh per block, though it is rated for 10–33 kV grids and its container is heavier, about 45 t. Where the storage connects to 400 V busbars, the cabinet-type scalepac from 1.016 MWh fits better.

Request a price and lead time

The manufacturer scalecube i3 grid-scale BESS block 7.25 MWh / 4.6 MVA. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

How much usable energy does one scalecube i3 block deliver?

A BESU block of 2 battery containers and 1 PCS delivers 7,250 kWh on the MV AC side at 4,600 kVA.

What grid voltage does scalecube i3 connect to?

To 10–36 kV, 50 Hz grids through a 4.6 MVA oil-immersed transformer, with a grid frequency range of 47–53 Hz.

Does scalecube i3 support grid-forming operation?

Yes, the 4,600 kVA inverter runs grid-following and grid-forming, the latter as a virtual synchronous machine.

How loud is a scalecube i3 plant?

Sound power is 85 ± 3 dB(A) for the battery container and 91 ± 3 dB(A) for the PCS, about 85 dB(A) with sound reduction.

Which protocols link scalecube i3 to the control room?

Modbus TCP/IP as standard, plus Modbus RTU, IEC 60870-5-104 and IEC 60870-5-101 via the IAU.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.