BATTERY ENERGY STORAGE SYSTEMS (BESS)
The manufacturer scalecube i4 grid-scale BESS block 10.4 MWh / 4.6 MVA
Country: Germany · Model: scalecube i4
One BESU block of the scalecube i4 battery energy storage system delivers 10.378 MWh of usable energy at 4,600 kVA and contains 2 battery containers and 1 PCS. Compared with scalecube i3, this version runs on 530 Ah LFP cells and stores noticeably more per container. The inverter, transformer and MV switchgear come in the package and suit 10–33 kV, 50 Hz grids.
- Cells
- LFP prismatic 530 Ah
- Container energy
- 5,644 kWh nominal
- BESU block
- 2 battery containers + 1 PCS, 10.378 MWh usable, 4,600 kVA
- Grid voltage
- 10–33 kV, 50 Hz
Technical specifications
| Cells | LFP prismatic 530 Ah |
|---|---|
| Container energy | 5,644 kWh nominal |
| BESU block | 2 battery containers + 1 PCS, 10.378 MWh usable, 4,600 kVA |
| Grid voltage | 10–33 kV, 50 Hz |
| Inverter | 4,600 kVA, 690 V, efficiency up to 99.2% |
| Container | 20 ft, IP55, liquid cooling, ~45 t |
| Operating temperature | −25…+45 °C |
| Battery standards | IEC 62619, IEC 62933-5-2, UL 1973, UL 9540, UL 9540A, NFPA 855 |
| More from the manufacturer’s documentation | |
| Container dimensions (H × W × D) | 2.896 × 6.058 × 2.438 m |
| BESU layout area (W × D) | 18.6 × 16.2 m (300.3 m²), minimum for service |
| Scaling steps | From 11.28 MWh / 4.6 MVA |
| Max. charge/discharge power | 0.5P |
| Self-discharge | ≤ 3.5% per month (DC decoupled) |
| Sound power level | Battery container 81 ± 3 dB(A); PCS 91 ± 3 dB(A) (without sound reduction; options available) |
| Humidity | < 95%, non-condensing |
| Installation altitude | Up to 2 km above sea level |
| Corrosion protection class | C5 |
| Design life | ≥ 15 years (depending on load profile) |
| Product/performance warranty | Up to 15 years |
| Grid frequency range | 47–53 Hz |
| Communication interfaces | Modbus TCP/IP; with IAU: Modbus RTU, IEC 60870-5-104, IEC 60870-5-101, digital/analog I/O card |
| Applications | Energy trading, multi-market optimization incl. balancing power and co-location, peak shaving, self-consumption optimization, external EMS control, backup power |
| PCS unit: dimensions (H × W × D), weight | 2.896 × 6.058 × 2.438 m, < 18 t |
| Inverter DC voltage range | 1,003–1,500 V |
| PCS IP rating | IP23D (control rooms) / IP54 (inverter electronics) |
| Inverter max. AC current | 3.85 kA |
| Power factor (cos φ) | 0 (ind.) … 1 … 0 (cap.) |
| Max. THD | < 3% at rated power |
| Transformer | Oil type, 4,600 kVA, Dy11, KNAN cooling, impedance 6%, tap changer ±2 × 2.5%, oil containment tray with filter |
| Transformer losses | No-load 4.14 kW, max. 38.7 kW (Eco Design, tier 2) |
| MV switchgear | Cable – cable – circuit breaker, definite-time overcurrent protection, short-circuit withstand 20 kA, 1 s |
| Color | Container RAL 9003; PCS RAL 9016 / RAL 7004 |
| ZEREZ certificates (VDE-AR-N 4110 / 4120 / 4130) | ZE-7ZWF-D8MS |
| Battery standards (additional) | CE, EN 61000-6-2, EN 61000-6-4, IEC 62477-1, IEC 63056, UN 38.3, UN 3536, NFPA 69 |
| Inverter standards | CE, IEC/EN 62109-1/-2, VDE-AR-N 4110/4120/4130, IEC 61000-6-2, EN 55011, CISPR 11, CSC |
| Transformer and switchgear standards | EN 50588-1, IEC 60076; IEC 62271-200, IEC 62271-202 |
| Customs codes (for reference) | |
| HS code | 8507.60 |
| UKTZED code (Ukraine) | 8507600000 |
| CN code (EU) | 85076000 |
Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.
Description
Each 20 ft container holds 5,644 kWh nominal in a 2.896 × 6.058 × 2.438 m body, with liquid cooling, IP55 protection and a weight of about 45 t. The 4,600 kVA inverter at 690 V takes 1,003–1,500 V DC, reaches up to 99.2% efficiency and supports grid-forming operation. Maximum AC current is 3.85 kA, and the power factor is adjustable from 0 inductive through 1 to 0 capacitive. Self-discharge stays at or below 3.5% per month with the DC side disconnected. The battery part complies with IEC 62619, IEC 62933-5-2, UL 1973, UL 9540 and UL 9540A, as well as NFPA 855, IEC 63056 and NFPA 69. Operating temperatures run from −25 to +45 °C, with C5 corrosion resistance.
How to choose
At the same 4,600 kVA, an i4 block stores 10.378 MWh against 7,250 kWh for scalecube i3, so it discharges longer at rated power. If the grid voltage is above 33 kV, scalecube i3 with its range up to 36 kV is the one to take. The system grows in steps from 11.28 MWh / 4.6 MVA, and one BESU with its service zone occupies 18.6 × 16.2 m (300.3 m²).
Request a price and lead time
The manufacturer scalecube i4 grid-scale BESS block 10.4 MWh / 4.6 MVA. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
What is the usable energy of a scalecube i4 block?
A BESU block of 2 battery containers and 1 PCS gives 10.378 MWh of usable energy at 4,600 kVA.
What cells are used in scalecube i4?
Prismatic 530 Ah LFP cells, with 5,644 kWh nominal energy per container.
How much does a scalecube i4 container weigh?
The 20 ft liquid-cooled IP55 battery container weighs about 45 t, and the PCS unit less than 18 t.
What is the noise level of scalecube i4?
Sound power is 81 ± 3 dB(A) for the battery container and 91 ± 3 dB(A) for the PCS without sound reduction, which is available as an option.
Similar products
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.