Reserva Pro — high-voltage LFP battery 12–32 kWh (up to 128 kWh)

Built from 3–8 modules per tower, the Reserva Pro high-voltage LFP battery gives 11.9–31.9 kWh of usable capacity, and parallel towers reach 128 kWh. This energy storage system goes into large homes and commercial and agricultural sites that need backup power and black start.

Usable capacity
11.9–31.9 kWh (3–8 modules per tower)
Nominal voltage
212.52–566.72 V
Cell chemistry
lithium iron phosphate (LFP)
Max. current
50 A

Technical specifications

Usable capacity11.9–31.9 kWh (3–8 modules per tower)
Nominal voltage212.52–566.72 V
Cell chemistrylithium iron phosphate (LFP)
Max. current50 A
Parallel operationup to 4 towers, up to 128 kWh
Ingress protectionIP65
Ambient temperature−20…+50 °C
Dimensions / weight775–1575 × 579 × 449 mm; 126–306 kg
StandardsVDE 2510-50, IEC 62619:2022, IEC 62040-1, CE, RCM, UN38.3
Interface / warrantyModbus RS485; 10 years (80% SOH)
More from the manufacturer’s documentation
Compatible invertersPrimo GEN24 Plus, Symo GEN24 Plus, Verto Plus
Operating voltage range165–240.9 V (12.0); 220–321.2 V (16.0); 275–401.5 V (20.0); 330–481.8 V (24.0); 385–562.1 V (28.0); 440–642.4 V (32.0)
Safety classII
Max. altitude2,000 m
Permissible humidity5–95 %
Installationindoor and protected outdoor areas
DC connectionStäubli MC4 Evo Stor
Battery module3.98 kWh; 70.84 V (55–80.3 V); 160 × 570 × 440 mm; 36 kg
BMS225 × 570 × 440 mm; 10 kg; inverter communication CAN / Modbus (RS485), module communication ISO-SPI
Base70 × 579 × 449 mm; 8 kg
Customs codes (for reference)
HS code8507.60
UKTZED code (Ukraine)8507600000
CN code (EU)85076000

Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.

Description

Cells and modules are manufactured in Europe. Each module weighs 36 kg and stores 3.98 kWh at 70.84 V, and the modules stack on a base together with the BMS unit. Tower nominal voltage is 212.52–566.72 V, maximum current is 50 A, and up to 4 towers run in parallel. The BMS talks to the inverter over CAN or Modbus RS485, and the DC power line runs on Stäubli MC4 Evo Stor connectors. The IP65 enclosure is rated for ambient temperatures from −20 to +50 °C and can stand indoors or in a sheltered outdoor spot. It measures 775–1575 × 579 × 449 mm and weighs 126–306 kg, so a full tower needs a floor that carries that load. The battery meets VDE 2510-50, IEC 62619:2022, IEC 62040-1, CE, RCM and UN38.3.

How to choose

Versions are named by capacity, from the Reserva Pro 12.0 with 3 modules to the 32.0 with 8, and every added module raises the tower operating voltage. With the three-phase Verto Plus this battery charges and discharges at up to 28.3 kW, which makes it the match for 25–33.3 kW sites. A house with a 3–6 kW Primo GEN24 is usually served by the compact Reserva with 6.31–15.79 kWh and 32 A.

Request a price and lead time

Reserva Pro — high-voltage LFP battery 12–32 kWh (up to 128 kWh). We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What is the maximum capacity of a Reserva Pro system?

Up to 128 kWh with 4 towers in parallel, and one tower gives 11.9–31.9 kWh.

What is the maximum current of the Reserva Pro battery?

50 A at a nominal voltage of 212.52–566.72 V.

What warranty does Reserva Pro storage carry?

10 years with 80% SOH retained.

Can Reserva Pro be installed in an unheated garage?

Yes, the IP65 enclosure runs from −20 to +50 °C at 5–95 % humidity, and a sheltered outdoor spot is also allowed. Installation altitude is up to 2,000 m.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.