BATTERY ENERGY STORAGE SYSTEMS (BESS)
DataSafe Noir — lithium-ion storage system for three-phase data center UPS
Country: USA · Model: DataSafe Noir
DataSafe Noir is built from lithium-ion cabinets at 512–614 V DC, each holding 500–600 kW for 5 minutes even at end of life. The system connects to three-phase data center UPS units and scales in modules up to 3 MW.
- Chemistry
- lithium-ion
- DC voltage
- 512–614 V
- Cabinet power
- 500–600 kW for 5 min (end of life)
- Scalability
- modular up to 3 MW
Technical specifications
| Chemistry | lithium-ion |
|---|---|
| DC voltage | 512–614 V |
| Cabinet power | 500–600 kW for 5 min (end of life) |
| Scalability | modular up to 3 MW |
| Interfaces | CAN, Ethernet, RS485 |
| Safety | multi-level protection at cell, module and system level |
| Customs codes (for reference) | |
| HS code | 8507.60 |
| UKTZED code (Ukraine) | 8507600000 |
| CN code (EU) | 85076000 |
Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.
Description
The high energy density of lithium shrinks the battery room compared with lead racks of the same power. The cabinet power rating is given for end of life, so the degradation margin is already built into the sizing. Variable load, including AI clusters with sharp consumption spikes, is easier on lithium than on lead. Protection works on three levels, separately at cell, module and system. Communication with the UPS and monitoring runs over CAN, Ethernet and RS485, so battery status shows up in the building control room. The 512–614 V window is matched to the DC input of the specific UPS, and compatibility is checked before ordering.
How to choose
The cabinet count follows from UPS power and required runtime, and at 5 minutes one cabinet covers 500–600 kW. Halls up to 3 MW grow by adding modules without replacing installed cabinets. If the UPS is set up for lead, the alternatives are DataSafe XE TPPL blocks for discharges under 5 minutes or flooded DataSafe DX at 300–1,915 Ah.
Request a price and lead time
DataSafe Noir — lithium-ion storage system for three-phase data center UPS. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
What DC voltage does DataSafe Noir use?
The operating window is 512–614 V. It must match the permitted DC input of the three-phase UPS.
How much power does one DataSafe Noir cabinet hold?
A cabinet delivers 500–600 kW for 5 minutes, and that figure is rated at end of life.
How far does DataSafe Noir scale?
It scales in modules up to 3 MW, with cabinets added as data center load grows.
What communication interfaces does DataSafe Noir have?
CAN, Ethernet and RS485. Through them the battery exchanges data with the UPS and the monitoring system.
Is DataSafe Noir suitable for AI workloads?
Yes, it is built for data centers with variable load, AI clusters with sharp consumption spikes included.