The manufacturer scalepac outdoor all-in-one storage system for C&I from 1 MWh

The scalepac outdoor storage system is assembled from all-in-one cabinets of 254 kWh, and the minimum system of 4 blocks gives 1.016 MWh at 500 kVA and up. The cabinets stand on a commercial or industrial (C&I) site and connect directly to the 0.4 kV grid. The supplied Application Unit runs peak shaving, consumption optimization and electricity trading.

Cells
LFP prismatic 306 Ah
Block energy
254 kWh nominal (228.6 kWh usable at 90% DoD)
System
from 1.016 MWh (4 blocks), up to 16 blocks
Power
from 500 kVA, step ~125 kVA; ≤125 kVA per block

Technical specifications

CellsLFP prismatic 306 Ah
Block energy254 kWh nominal (228.6 kWh usable at 90% DoD)
Systemfrom 1.016 MWh (4 blocks), up to 16 blocks
Powerfrom 500 kVA, step ~125 kVA; ≤125 kVA per block
Connection400 V (3L, N, PE)
Efficiency (AC, round-trip)~90%
Overload110% for at least 10 min
Protection ratingIP54, corrosion resistance C5
Operating temperature−20…+50 °C
StandardsEN 62619, UN 38.3, VDE-AR-N 4105/4110, EN 50549-1
More from the manufacturer’s documentation
Unit dimensions (H × W × D)2,250 × 1,420 × 1,425 mm
System dimensions (H × W × D)2,250 × 5,680 × 1,425 mm (4 units) … 2,250 × 11,360 × 1,425 mm (8 units)
Weight< 2.8 t per unit; < 11.2 t (scalepac4) … < 22.4 t (scalepac8)
Configurations (nominal / usable energy)scalepac4 — 1,016 / 914 kWh; scalepac5 — 1,270 / 1,143 kWh; scalepac6 — 1,524 / 1,372 kWh; scalepac7 — 1,778 / 1,600 kWh; scalepac8 — 2,032 / 1,828 kWh
Max. system charge/discharge power≤ 500 kVA (scalepac4), ≤ 625 kVA (scalepac5), ≤ 750 kVA (scalepac6), ≤ 875 kVA (scalepac7), ≤ 1,000 kVA (scalepac8)
Nominal current per unit217 A
Grid voltage tolerance−15% to +10%
Grid typeTN-S, TN-C, TN-C-S
Operating modeGrid-parallel operation
CoolingPCS air-cooled, battery packs liquid-cooled (R134a)
DeratingAbove 40 °C
Installation altitudeUp to 3,000 m above sea level
Cycle lifeOver 6,000 cycles
Expected lifetime≥ 15 years
Product/performance warrantyUp to 10 years
Guaranteed energy throughput until EOL10 years or 2.5 GWh (1 unit) … 20 GWh (scalepac8), whichever occurs first
Fire protectionSmoke and heat detectors, aerosol extinguishing, dry-pipe water connection, pressure relief valve; fire resistance up to 1 h
Cable entryBottom or rear, cross-section up to 70 mm²
Communication interfacesModbus TCP/IP, remote control protocols, cloud connection
ScalingMin. 4 units (5,600 mm), up to 8 units side by side, up to 16 units per IAU
Inverter IP ratingIP20 (inside enclosure)
AlarmsAcoustic and visual
ColorRAL 7035 (light gray), RAL 2004 (orange)
Inverter standardsEN 62109-1, EN 62040-2, EN 61439-1, EN 61439-2
Other standards and directivesEN 61000-6-2, EN 61000-6-4, 2006/66/EG, TOR Generator Type A/B, 2014/53/EU (RED), 2014/30/EU (EMC), 2014/35/EU (LVD)
Manufacturer quality managementISO 9001:2015 (TÜV Rheinland, certificate valid until 2028-10-12)
Customs codes (for reference)
HS code8507.60
UKTZED code (Ukraine)8507600000
CN code (EU)85076000

Specifications are taken from the manufacturer’s technical documentation. Updated . Customs codes are for reference only; the final code is determined at customs declaration for the specific model.

Description

Each cabinet holds a battery of prismatic 306 Ah LFP cells, an inverter (PCS), a BMS and climate equipment, with the PCS air-cooled and the battery packs on R134a liquid cooling. At 90% depth of discharge a cabinet delivers 228.6 kWh, and block power goes up to 125 kVA. The output is three-phase 400 V (3L, N, PE), and the unit runs grid-parallel with grid voltage deviation from −15% to +10%. AC round-trip efficiency is about 90%, and a 110% overload is allowed for at least 10 min. The IP54 enclosure with C5 corrosion resistance works from −20 to +50 °C, with power derated above 40 °C. Smoke and heat detectors, aerosol extinguishing and a pressure relief valve sit inside. The cabinets comply with EN 62619, UN 38.3, VDE-AR-N 4105/4110 and EN 50549-1.

How to choose

The number of cabinets sets energy and power together, so sizing starts from the daily load profile. A scalepac4 has 914 kWh usable and up to 500 kVA, while a scalepac8 reaches 1,828 kWh and 1,000 kVA in a row 11,360 mm long weighing up to 22.4 t. For a 10–36 kV network and megawatt loads, take the scalecube i3 grid block with 7,250 kWh and 4,600 kVA or the scalecube i4 with 10.378 MWh.

Request a price and lead time

The manufacturer scalepac outdoor all-in-one storage system for C&I from 1 MWh. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What is the usable capacity of one scalepac cabinet?

Nominal block energy is 254 kWh, usable energy 228.6 kWh at 90% depth of discharge.

How many scalepac cabinets can be combined in one system?

From 4 blocks (1.016 MWh, 500 kVA) up to 16 blocks per IAU, with power growing in steps of about 125 kVA.

What outdoor temperature range does the scalepac storage system handle?

From −20 to +50 °C, in an IP54 enclosure with C5 corrosion resistance.

What cable goes to a scalepac cabinet?

Nominal current per block is 217 A, with bottom or rear entry up to 70 mm². The grid type is TN-S, TN-C or TN-C-S.

How many cycles does the scalepac battery last?

Over 6,000 cycles, with an expected lifetime of at least 15 years.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.