Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

BURNERS AND GAS VALVES

GasMultiBloc MBC (65/120, 300/700/1200-SE/N/VEF, WhirlWind WND) — compact multiblocks with servo-controlled regulator

MBC compact multiblocks combine a micro filter, two class A valves and a servo-controlled pressure regulator in one body. They are for forced-draught and premix burners of boilers and air heaters. Types range from MBC-65 to MBC-1200, pressure up to 360 mbar, protection rating IP54.

MBC-65/120
length 105 mm; pmax 200/360 mbar (version N 65/100 mbar); regulator EN 88 class C
MBC-300/700/1200-SE/N
pmax 360 mbar; outlet 0–80 mbar; modulation
MBC-300/700/1200-VEF
pmax 360 mbar; outlet up to 300 mbar; V = 0.4:1…3:1
MBC-WND (WhirlWind)
9–1000 kW; inlet 65/100 mbar; modulation up to 1:10

Technical specifications

MBC-65/120length 105 mm; pmax 200/360 mbar (version N 65/100 mbar); regulator EN 88 class C
MBC-300/700/1200-SE/Npmax 360 mbar; outlet 0–80 mbar; modulation
MBC-300/700/1200-VEFpmax 360 mbar; outlet up to 300 mbar; V = 0.4:1…3:1
MBC-WND (WhirlWind)9–1000 kW; inlet 65/100 mbar; modulation up to 1:10
Valves2 × class A per EN 161 (group 2)
Filtermicro filter
ProtectionIP54
Ambient temperature−15…+60 °C
American versionsMBC-1000/2500/4000 SE, VEF, VV (UL, FM, CSA)

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

MBC-65 and MBC-120, 105 mm long, are intended for single-stage operation; their maximum pressure is 200 and 360 mbar (20 and 36 kPa), and the N versions are rated for 65 and 100 mbar. The valves are class A to EN 161 (group 2), the regulator is servo-controlled to EN 88 class C, with zero or constant pressure, fast or slow opening and a main flow limiter. Ambient temperature is from −15 to +60 °C. MBC-300, MBC-700 and MBC-1200 in SE and N versions work at 360 mbar with an outlet pressure of 0–80 mbar (0–8 kPa) for modulating burners with mechanical or electronic gas/air ratio control. VEF versions have a pneumatic ratio of 0.4:1…3:1, an outlet up to 300 mbar, zero correction and an internal gas line. Connection is by ISO 7/1 flanges or NPT. The WhirlWind system (MBC-WND) combines a swirl plate, a Venturi tube and a signal amplifier for burners from 9 to 1000 kW, with inlet pressure of 65 mbar for WND 65 and 100 mbar for WND 120–1200, and modulation up to 1:10.

How to choose

If the burner is single-stage and space is limited, MBC-65 or MBC-120 is taken. For a modulating burner with an external ratio system, MBC-300, 700 or 1200 in the SE or N version is suitable, and when the multiblock itself must hold the ratio, the VEF version. For premix and forced-draught burners without selecting an injector for the gas family, MBC-WND is taken. Pressure switches and VPS are added separately. For the USA there are MBC-1000/2500/4000 in the SE, VEF and VV variants.

Request a price and lead time

GasMultiBloc MBC (65/120, 300/700/1200-SE/N/VEF, WhirlWind WND) — compact multiblocks with servo-controlled regulator. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What is the maximum pressure of MBC-65 and MBC-120?

200 mbar (20 kPa) for MBC-65 and 360 mbar (36 kPa) for MBC-120. The N versions are rated for 65 and 100 mbar.

In what range is the MBC-SE outlet pressure adjustable?

MBC-300, 700 and 1200 in SE and N versions give an outlet of 0–80 mbar (0–8 kPa) at an inlet of 360 mbar.

What gas/air ratio does MBC-VEF have?

A transmission ratio from 0.4:1 to 3:1, outlet pressure up to 300 mbar, with zero correction.

What burner output is WhirlWind suitable for?

MBC-WND is used on burners from 9 to 1000 kW, with modulation up to 1:10.

What are the protection rating and ambient temperature?

IP54 and from −15 to +60 °C.

Similar products

Burners and gas valves

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.