VPS 504, VPS 508 and VPM-VC gas valve tightness control systems per EN 1643

VPS 504, VPS 508 and VPM-VC systems check the tightness of two consecutive gas shut-off valves before burner start-up or after shutdown per EN 1643. VPS works by pressure rise up to 50 kPa, the check takes 10–36 s, and VPM-VC compares pressures. They are installed on gas burners and gas engines.

Standard
EN 1643
VPS 504/508
for multiblocs MB, DMV and single valves up to DN 80; test volume ≤ 4 l (VPS 504) / 8 l (VPS 508)
VPS principle
pressure rise, up to 50 kPa inlet pressure
VPS test time
10–36 s

Technical specifications

StandardEN 1643
VPS 504/508for multiblocs MB, DMV and single valves up to DN 80; test volume ≤ 4 l (VPS 504) / 8 l (VPS 508)
VPS principlepressure rise, up to 50 kPa inlet pressure
VPS test time10–36 s
VPM-VC principlepressure comparison with one or two pressure switches; no limit on pressure and volume
Power supplyVPS 24 V DC (gas engines) and mains versions; VPM-VC 115/230 V AC or 24 V DC
Indicationtightness/leak LED, external fault signaling
ApprovalsEU type per GAR and PED, EAC, UL, FM, CSA

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

VPS 504 is designed for multiblocs MB, double valves DMV and single valves up to DN 80, with and without a bypass. The test volume is not more than 4 l, no setup on site is needed, and operation does not depend on the residual pressure within the permissible range. VPS 508 works on the same principle for a volume of up to 8 l. The state is shown by an LED, an external fault signal is possible for series 02, 04 and S05, and a group signal for S01. The connection is plug-in for S01–S03 per DIN 4791 without rewiring, and for S04 and S05 screw terminals through a PG 13.5 cable gland; a 24 V DC version for gas engines is available. VPM-VC checks the valves together with one or two pressure switches without limits on pressure and volume. The sequence, filling and reset options are set by the user, and the module works alone or with a PLC, at 115/230 V AC or 24 V DC. The systems meet the requirements of EN 746-2 and ISO 13577, and VPM complies with the Machinery Regulation (EU) 2023/1230 and the LVD and EMC directives.

How to choose

The choice depends on the volume between the valves. Up to 4 l VPS 504 is suitable, up to 8 l VPS 508, and both work with an inlet pressure of up to 50 kPa. If the pressure or volume exceeds these limits, or a flexible test program together with a PLC is needed, VPM-VC is used. For a gas engine at 24 V DC there is a version of both types. At the inlet of the gas train, a GF filter is installed before the valves.

Request a price and lead time

VPS 504, VPS 508 and VPM-VC gas valve tightness control systems per EN 1643. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

How long does the VPS tightness check take?

From 10 to 36 seconds. The result is shown by a tightness or leak LED.

What is the test section volume of VPS 504 and VPS 508?

Not more than 4 l for VPS 504 and up to 8 l for VPS 508.

What is the supply voltage of VPM-VC?

115/230 V AC or 24 V DC. The module works on its own, with a PLC or with a burner control unit.

What certificates does the system have?

EU type per GAR and PED, UKCA, AGA, EAC, UL, FM and CSA.

Similar products

Burners and gas valves

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.