Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

LOW-VOLTAGE EQUIPMENT

А572 — current monitoring relay with digital display

20–600 А (with Т-0,66 CT) · 49–61 Hz · 0–20 mA output · (24 ± 4) V supply

The А572 is a current monitoring relay. It monitors the RMS value of AC current through an external current transformer. The relay receives a 0 to 1 V signal from the secondary winding of the loaded transformer. This signal is proportional to the primary current. The current value is shown on a digital display and on a remote analogue indicator. If the current goes outside the set levels, the relay generates two control commands. It also issues a separate readiness command. The output circuits switch 5–250 V AC and 5–30 V DC at currents from 1 mA to 1 A. A 0–20 mA DC analogue output, proportional to the monitored current, is also provided. Two control inputs accept a primary-current switch-on command (for example, motor start) and a blocking command. The supply is (24 ± 4) V and current consumption is no more than 100 mA. The frequency range is 49–61 Hz, and the relay is rated for continuous operation. It is used for motor start monitoring and in interlocking circuits at industrial sites.

Rated monitored current (with Т-0,66 CT)
20, 30, 40, 50, 75, 100, 150, 200, 300, 400, 600 A
CT secondary signal voltage
0 to 1 V
Monitored current frequency range
49–61 Hz
Switched voltage, AC
5–250 V

Technical specifications

Rated monitored current (with Т-0,66 CT)20, 30, 40, 50, 75, 100, 150, 200, 300, 400, 600 A
CT secondary signal voltage0 to 1 V
Monitored current frequency range49–61 Hz
Switched voltage, AC5–250 V
Switched voltage, DC5–30 V
Switched current1 mA to 1 A
Control input currentmax. 10 mA
Supply voltage(24 ± 4) V
Current consumptionmax. 100 mA
Analogue output signal0–20 mA DC
Inputs and outputs2 control inputs, 2 output commands, 1 readiness command
Indicationdigital and remote analogue
Operating modecontinuous
Overall dimensions53x35x64 mm
Weight0.1 kg

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

The rated monitored current is set by the current transformer. With a Т-0,66 transformer it is selected from the series 20, 30, 40, 50, 75, 100, 150, 200, 300, 400, 600 А. Choose the value closest to the operating current of the monitored line or motor. For the switched circuits, keep within the limits: up to 250 V AC or 30 V DC, and no more than 1 A.

Similar products

Low-voltage equipment

Request a price and lead time

А572 — current monitoring relay with digital display. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.