Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

LOW-VOLTAGE EQUIPMENT

B15 / B35 / B50 / DMP-FTV / GE 230V — automatic 0.4 kV reactive power compensation units without reactors

B15, B35, B50, DMP-FTV and GE 230V are automatic 0.4 kV reactive power compensation units without reactors, from 10.2 kVAr to over 1000 kVAr. They are intended for networks with low and medium harmonic levels.

Mains voltage
400–415 V (GE 230V — 230 V)
Power
10.2 kVAr … over 1000 kVAr (G3E … G8E in several sections)
Permissible mains THD(I)
B15 — 15 %; B35, GE 230V — 25 %; B50 — 35 %; DMP-FTV — 40 %
Capacitors
MKP; B50 and DMP-FTV — Heavy Duty twin-element

Technical specifications

Mains voltage400–415 V (GE 230V — 230 V)
Power10.2 kVAr … over 1000 kVAr (G3E … G8E in several sections)
Permissible mains THD(I)B15 — 15 %; B35, GE 230V — 25 %; B50 — 35 %; DMP-FTV — 40 %
CapacitorsMKP; B50 and DMP-FTV — Heavy Duty twin-element
ControllerBMR4 / BMR6 / HPR6 / HPR12
EnclosuresG3E, G4E (IP30), G4RM (IP40), G6E, G8E, G9E (IP31)
ContactorsAC6-b with pre-insertion resistors
MonitoringCCS (standard on DMP-FTV)
StandardsIEC/EN 61439-1/2, IEC/EN 61921; capacitors IEC/EN 60831-1/2 (IMQ)

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

A microprocessor controller measures reactive power in four quadrants and switches the steps with contactors, so the set power factor is held without penalties for reactive energy. B15 is for 400 V networks with current THD up to 15 % and an 8-hour duty cycle, B35 is for industry with THD up to 25 %, and B50 is for THD up to 35 % (up to 80 % on the capacitors) and continuous operation with twin-element Heavy Duty capacitors. DMP-FTV is designed for THD up to 40 %, small photovoltaic plants and continuous duty, with Heavy Duty capacitors and CCS monitoring as standard, while GE 230V works in three-phase 230 V networks. The range starts at 10.2 kVAr (G3E, 3 steps of 3.4 kVAr), then 50–100 kVAr (G3E/G4E), 125–250 kVAr (G4RM), 300–500 kVAr (G6E) and 525–1050 kVAr and more (G8E in several sections), with up to 16 steps. Controllers are BMR4, BMR6, HPR6 and HPR12. Cabinets are made of sheet steel with an epoxy coating RAL 7035, IP30 (G3E, G4E), IP40 (G4RM), IP31 (G6E, G8E, G9E), IP20 inside, and the steps in G6, G8 and G9 slide out to the front. The units have a three-pole isolator with door interlock, NH-00 gG 100 kA fuses, AC6-b contactors with pre-insertion resistors and low-smoke FS17 cables. The capacitors are MKP with pressure protection, with losses up to 0.4 W/kVAr. Tripping occurs on high THDi, overheating above 50 °C, and minimum or maximum voltage, the dry contact operates above 70 °C, and ventilation is natural up to 200 kVAr and forced above that. Standards are IEC/EN 61439-1/2 and 61921, capacitors IEC/EN 60831-1/2 (IMQ V1927), operation at −5…+40 °C at altitudes up to 1000 m.

How to choose

The series is chosen by the current THD of the network. B15 suits up to 15 %, B35 and GE 230V up to 25 %, B50 up to 35 %, and DMP-FTV up to 40 %. The enclosure from G3E to G8E depends on the power, and for continuous duty with higher harmonics B50 or DMP-FTV with twin-element Heavy Duty capacitors is used.

Request a price and lead time

B15 / B35 / B50 / DMP-FTV / GE 230V — automatic 0.4 kV reactive power compensation units without reactors. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What THD is permissible for B15, B35 and B50?

B15 up to 15 %, B35 up to 25 %, B50 up to 35 % of the mains current.

What is the smallest unit power?

10.2 kVAr, in a G3E enclosure with 3 steps of 3.4 kVAr.

What is the enclosure protection rating?

IP30 for G3E and G4E, IP40 for G4RM, IP31 for G6E, G8E and G9E.

What is DMP-FTV intended for?

For THD up to 40 %, small photovoltaic plants and continuous duty, with CCS as standard.

Similar products

Low-voltage equipment

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.