Bolted connectors and cable lugs for networks up to 1 kV, 1.5–300 mm²
Country: Germany · Model: LV bolted connectors and lugs
Bolted connectors and cable lugs for cables up to 1 kV for cross-sections of 1.5–300 mm². Conductors of classes 1 and 2 per EN 60228, tested to IEC 61238-1-1. The connectors are designed for heat-shrink joints per DIN SPEC 47640.
- Purpose
- connection and termination of low-voltage cable conductors
- Conductor cross-section
- 1.5–16 mm² Cu; 4–50 / 25–95 / 25–150+185 SE / 25–185+240 SE / 95–240+300 SE mm²
- Conductor classes
- 1 and 2 per EN 60228, including 120° sector without crimping
- Tests
- IEC 61238-1-1, class 1 (mech.) and class A (electr.)
Technical specifications
| Purpose | connection and termination of low-voltage cable conductors |
|---|---|
| Conductor cross-section | 1.5–16 mm² Cu; 4–50 / 25–95 / 25–150+185 SE / 25–185+240 SE / 95–240+300 SE mm² |
| Conductor classes | 1 and 2 per EN 60228, including 120° sector without crimping |
| Tests | IEC 61238-1-1, class 1 (mech.) and class A (electr.) |
| Applicability | for heat-shrink joints per DIN SPEC 47640 |
| Connector versions | inspection hole or oil stop; shear bolts or set screws |
| Connector length | 30–110 mm |
| Lugs | standard and NEMA (2 holes), with shear bolts only |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
Cross-sections range from 1.5–16 mm² for copper to 95–240+300 mm² for sector conductors. The enlarged heart-shaped conductor channel makes installation easier, because crushed or protruding conductor ends enter easily and do not catch. Shear bolts have one or two shear points, protrude minimally after installation, and the large hexagonal head does not jam in the tool. Instead of them, set screws with an internal hexagon can be ordered, which allow disassembly. A rotating friction disc at the base of the bolt does not damage the conductor wires and maintains contact pressure, and the transverse grooves of the channel break the oxide film and increase the pull-out force. The connectors come with an inspection hole or with an oil stop that blocks the path of liquid and gas. Lugs are made in standard and NEMA versions with two holes.
How to choose
The deciding parameters here are the cross-section and the conductor class. For copper 1.5–16 mm² there is a separate group, and for larger cross-sections four ranges up to 95–240+300 mm². An oil stop is taken where a barrier for liquid and gas is needed, and an inspection hole where it is important to see the conductor position. For taps without stripping the insulation, see the LV piercing connectors for 1–240 mm² or ISICOMPACT, and for connection to transformer bushings and busbars 2DIREKT up to 4 kA.
Request a price and lead time
Bolted connectors and cable lugs for networks up to 1 kV, 1.5–300 mm². We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
What conductor cross-sections are these connectors designed for?
From 1.5–16 mm² for copper to 95–240+300 mm² for sector conductors, including classes 1 and 2 per EN 60228.
What standards are the connectors tested to?
To IEC 61238-1-1, mechanical class 1 and electrical class A. They are designed for heat-shrink joints per DIN SPEC 47640.
How does a connector with an oil stop differ from one with an inspection hole?
The oil stop serves as a barrier for liquid and gas, while the inspection hole makes it possible to see the conductor. Both versions come with shear bolts or with screws.
Are cable lugs available in standard and NEMA versions?
Yes, lugs are made in standard and NEMA versions with two holes, with shear bolts only.