Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

LOW-VOLTAGE EQUIPMENT

БРГ-312 — galvanic isolation signal converter with two analogue outputs

accuracy ±0.2 % · 2 independent analogue outputs · outputs 0–5, 0–20, 4–20 mA, 0–10 V · IP20, DIN rail

The БРГ-312 is a galvanic isolation and signal conversion block with one analogue input and two independent analogue outputs. It accepts signals from primary transducers. These can be current inputs of 0–5, 0–20, 4–20, -5…5 or -20…20 mA, or voltage inputs of 0–10 V, -10…10 V, 0–100 mV or -100…100 mV. It also handles ТСМ, ТСП, Pt100, Pt500 and Pt1000 resistance thermometers, type K, L, N, J, S, R, B, T, E, A-1, A-2 and A-3 thermocouples, and resistance up to 2500 Ω. The input is converted into standardised 0–5 mA, 0–20 mA, 4–20 mA or 0–10 V signals. Input, output and supply circuits are galvanically isolated, with an isolation voltage of 500–1500 V. Conversion accuracy is ±0.2 %. Input type and scaling are configured via USB. The unit monitors for open circuit, short circuit and out-of-range signals. It is powered from 24 V or 230 V and housed in an IP20 DIN-rail enclosure. Typical uses include automation, monitoring, control and dispatching of industrial processes.

Current input signals
0–5 mA, 0–20 mA, 4–20 mA, -5…5 mA, -20…20 mA
Voltage input signals
0–10 V, -10…10 V, 0–100 mV, -100…100 mV
Resistance thermometers
ТСМ 50М, ТСМ 100М, ТСП 50П, ТСП 100П, Pt100, Pt500, Pt1000
Thermocouples
ТХА (K), ТХК (L), ТНН (N), ТЖК (J), ТПП 10 (S), ТПП (R), ТПР (B), ТМКн (T), ТХКн (E), ТВР-1 (A-1), ТВР-2 (A-2), ТВР-3 (A-3)

Technical specifications

Current input signals0–5 mA, 0–20 mA, 4–20 mA, -5…5 mA, -20…20 mA
Voltage input signals0–10 V, -10…10 V, 0–100 mV, -100…100 mV
Resistance thermometersТСМ 50М, ТСМ 100М, ТСП 50П, ТСП 100П, Pt100, Pt500, Pt1000
ThermocouplesТХА (K), ТХК (L), ТНН (N), ТЖК (J), ТПП 10 (S), ТПП (R), ТПР (B), ТМКн (T), ТХКн (E), ТВР-1 (A-1), ТВР-2 (A-2), ТВР-3 (A-3)
Resistance input signals0–150 Ω, 0–300 Ω, 0–1200 Ω, 0–2500 Ω
Output signals0–5 mA, 0–20 mA, 4–20 mA, 0–10 V
Number of outputs2 independent analogue
Accuracy±0.2 %
Supply voltage24 V, 230 V
Galvanic isolation voltage500–1500 V
Configuration interfaceUSB
ProtocolModbus RTU
Diagnosticsopen circuit, short circuit, out of range
Protection ratingIP20
MountingDIN rail
Dimensions100×23×115 mm
Weight0.2 kg
StandardsДСТУ IEC 60381-1, ДСТУ IEC 60381-2, ДСТУ 2858, ДСТУ EN IEC 60751, ДСТУ 2837, ДСТУ EN 60584-1, ДСТУ EN 60529, ДСТУ IEC 60654-1, ДСТУ IEC 60654-3
Replaces discontinuedБРГ-12

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

When ordering, specify the supply voltage: 24 V or 230 V. The input type is set in software via USB. It can be current, voltage, thermocouple, resistance thermometer or resistance. For each of the two outputs, choose the range: 4–20 mA for standard current loops, 0–5 mA or 0–20 mA for older systems, or 0–10 V for controller voltage inputs.

Similar products

Low-voltage equipment

Request a price and lead time

БРГ-312 — galvanic isolation signal converter with two analogue outputs. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.