БРГ-412 — two-channel galvanic isolation block for 4–20 mA signals
Country: Ukraine · Model: БРГ-412
2 channels · 4–20 mA input/output · 0.2 % error · loop-powered 18–36 V
The БРГ-412 is a two-channel galvanic isolation block for circuits carrying standardised 4–20 mA current signals. Each of its two independent channels accepts a passive input signal from a sensor or secondary transmitter and delivers an active 4–20 mA output, with inputs, outputs and the channels themselves isolated from one another. The galvanic isolation voltage is 500 V and the maximum conversion error is 0.2 %. The unit draws its power directly from the current loop at 18 to 36 V and drives loads of up to 500 Ω (nominal 250 Ω). The compact 76 x 26 x 115 mm housing weighs no more than 0.13 kg, mounts on a DIN rail and operates from −40 to +70 °C. Typical applications include process regulation and control systems, industrial automation (АСУ ТП), the energy and metallurgy sectors, measuring and computing systems and telemechanics, where it protects receiving equipment from potential differences and interference.
- Number of independent channels
- 2
- Input signal
- 4 to 20 mA (passive)
- Output signal
- 4 to 20 mA (active)
- Load resistance, max
- 500 Ω
Technical specifications
| Number of independent channels | 2 |
|---|---|
| Input signal | 4 to 20 mA (passive) |
| Output signal | 4 to 20 mA (active) |
| Load resistance, max | 500 Ω |
| Nominal load resistance | 250 Ω |
| Maximum input signal conversion error | 0.2 % |
| Additional reduced error limits | 0.2 % |
| Maximum input voltage drop | 36 V |
| Supply voltage from current loop | 18 to 36 V |
| Galvanic isolation voltage | 500 V |
| Mounting | DIN rail |
| Ambient temperature | −40 °C to +70 °C |
| Relative humidity | 30 to 80 % |
| Vibration resistance | version N2 to ГОСТ 12997 |
| Electromagnetic compatibility | ДСТУ IEC 61326-1:2002 |
| Dimensions (HxWxD) | 76 x 26 x 115 mm |
| Weight, max | 0.13 kg |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
How to choose
Choose the БРГ-412 for isolating passive 4–20 mA signals into an active 4–20 mA output with loads up to 500 Ω. For 0–5 mA or 0–10 V inputs with 0–10 V, 0–5 V or 4–20 mA outputs, consider the БРГ-21; for 4–20 mA circuits with an 800 Ω output load, the БРГ-422.
Similar products
Request a price and lead time
БРГ-412 — two-channel galvanic isolation block for 4–20 mA signals. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.