БУС-21 — phase-angle triac control unit
Country: Ukraine · Model: БУС-21
switching up to 600 V · load current up to 40 A · input 0-5 / 0-20 / 4-20 mA, 0-10 V · supply 220 V, 6 V·A
The БУС-21 is a single-channel phase-angle triac control unit for smooth power regulation in resistive and resistive-inductive loads. It accepts a standard analogue signal and, in every period of the mains voltage, sends a firing pulse to the triac at the corresponding conduction angle, thereby varying the RMS voltage across the load. The output uses an internal opto-triac without a built-in zero-crossing detector. Switched voltage is not more than 600 V AC (RMS) or DC, maximum load current is 40 A, conversion non-linearity is 10 % and turn-on time is 4 s. The unit is powered from 220 V and consumes 6 V·A. Three-level galvanic isolation separates input, output and supply circuits. The IP30 housing mounts on a DIN rail. Typical applications include the power generation, metallurgical and chemical industries, where the unit maintains process temperatures automatically or sets the power of electric heaters.
- Number of channels
- 1
- Input signal
- 0-5 mA (Rin = 200 Ω), 0-20 mA (Rin = 50 Ω), 4-20 mA (Rin = 50 Ω), 0-10 V (Rin = 20 kΩ)
- Output type
- internal opto-triac without built-in phase zero-voltage detector
- Control method
- phase-angle
Technical specifications
| Number of channels | 1 |
|---|---|
| Input signal | 0-5 mA (Rin = 200 Ω), 0-20 mA (Rin = 50 Ω), 4-20 mA (Rin = 50 Ω), 0-10 V (Rin = 20 kΩ) |
| Output type | internal opto-triac without built-in phase zero-voltage detector |
| Control method | phase-angle |
| Maximum switched voltage | not more than 600 V AC (RMS) or DC |
| Maximum load current | 40 A |
| Conversion non-linearity | 10 % |
| Turn-on time | 4 s |
| Supply voltage | 220 V |
| Mains frequency | 50 Hz |
| Power consumption | 6 V·A |
| Galvanic isolation | three-level (input, output, supply) |
| Load type | resistive, resistive-inductive |
| Versions | БУС-21-1 (0-5 mA), БУС-21-2 (0-20 mA), БУС-21-3 (4-20 mA), БУС-21-4 (0-10 V) |
| Degree of protection | IP30 |
| Mounting | DIN rail |
| Operating temperature | −40 °C to 70 °C |
| Relative humidity | 30 to 80 % (non-condensing) |
| Dimensions | 96 x 100 x 110 mm |
| Weight | 0.55 kg |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
How to choose
Select the version by control signal: БУС-21-1 for 0-5 mA input (Rin = 200 Ω), БУС-21-2 for 0-20 mA (Rin = 50 Ω), БУС-21-3 for 4-20 mA (Rin = 50 Ω) and БУС-21-4 for 0-10 V (Rin = 20 kΩ). The signal type should match the output of the controller or setpoint device.
Similar products
Request a price and lead time
БУС-21 — phase-angle triac control unit. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.