Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

LOW-VOLTAGE EQUIPMENT

B / AR / QSRB / AST capacitor banks for reactive power compensation

Capacitor banks for reactive power compensation are intended for 400 V, 50 Hz networks, with a 60 Hz version possible on request. The line includes automatic, fixed and fast thyristor-switched banks, including for networks with harmonics. They are installed at the plant input, in substations and workshop panels to reduce charges for reactive energy and relieve the transformer.

Voltage
400 V, 50 Hz (60 Hz on request)
Types
automatic B25/B35/B50, AR140/AR180 (with anti-resonance reactors); fixed QSRB25/QSRB35; static thyristor-switched AST
Protection degree
IP30/IP40
Capacitors
self-healing, metallized polypropylene

Technical specifications

Voltage400 V, 50 Hz (60 Hz on request)
Typesautomatic B25/B35/B50, AR140/AR180 (with anti-resonance reactors); fixed QSRB25/QSRB35; static thyristor-switched AST
Protection degreeIP30/IP40
Capacitorsself-healing, metallized polypropylene

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The automatic banks B25, B35 and B50 switch capacitor steps on a regulator signal according to the current cos φ. The AR140 and AR180 series are fitted with anti-resonance reactors, which protect capacitors from harmonic overload and prevent resonance with the network inductance. The fixed QSRB25 and QSRB35 compensate a constant reactive component, for example the no-load current of a transformer or a large motor. The static AST banks switch capacitors with thyristors without contacts, which is needed for rapidly varying loads such as welding or cranes. Capacitors of metallized polypropylene self-heal after a local breakdown. The cabinets have an IP30 or IP40 protection degree.

How to choose

The choice starts with the share of non-linear load. If the network has few frequency converters and rectifiers, ordinary automatic B25/B35/B50 are suitable. With noticeable harmonics AR140/AR180 with reactors are needed, and for rapidly varying loads the thyristor AST. The fixed QSRB25/QSRB35 is installed where reactive power hardly changes. When harmonics are strong, it is advisable to install an active filter alongside.

Request a price and lead time

B / AR / QSRB / AST capacitor banks for reactive power compensation. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What voltage are B and AR capacitor banks rated for?

For a 400 V, 50 Hz network, and a 60 Hz version is made on request.

Why do AR140 and AR180 banks have reactors?

Anti-resonance reactors shift the resonant frequency of the circuit below the harmonic frequencies, so the capacitors are not overloaded in networks with non-linear load.

When is the AST thyristor capacitor bank needed?

When the load changes within fractions of a second, for example during welding or motor starts. Thyristors switch the steps without current surges and contact wear.

What protection degree do B, AR and QSRB banks have?

The cabinets are made with IP30 or IP40 protection and are intended for closed electrical rooms.

What capacitors are used in AR and QSRB banks?

Self-healing capacitors of metallized polypropylene, which restore insulation after a local breakdown.

Similar products

Low-voltage equipment

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.