Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

LOW-VOLTAGE EQUIPMENT

RPC / RCM / RCL capacitor racks (withdrawable modules) for 0.4 kV reactive power compensation switchboards

The withdrawable capacitor racks RPC, RCM and RCL arrive on site as a ready 0.4 kV compensation step, in the RPC series from 25 to 100 kvar at 400 V. Three-phase sets of single-phase capacitors, a contactor and fuses are already mounted on a galvanized steel frame, and in anti-resonance versions a reactor as well, so a panel builder assembles from them a bank of the required power in their own cabinet.

Series
RPC (19″ data centre cabinets), RCM (G6E/G8E cabinets), RCL (G9E cabinets)
Versions
B15, B35, B50 (without reactors); AAR/100, AAR/600, AAR/6, AAR/138, AAR/D20 (with reactors)
RPC power
25–100 kvar at 400 V
Capacitors
MKP, 415/450 … 550/600 V, current overload 1.3 In

Technical specifications

SeriesRPC (19″ data centre cabinets), RCM (G6E/G8E cabinets), RCL (G9E cabinets)
VersionsB15, B35, B50 (without reactors); AAR/100, AAR/600, AAR/6, AAR/138, AAR/D20 (with reactors)
RPC power25–100 kvar at 400 V
CapacitorsMKP, 415/450 … 550/600 V, current overload 1.3 In
Reactors189 Hz (p = 7 %) or 138 Hz (p = 14 %), 6–6.5 W/kvar
FusesNH-00 gG, 100 kA
ContactorsAC6-b
Protection ratingIP00
StandardsIEC/EN 60831-1/2, EN 61921

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The RPC racks fit 19-inch cabinets of data centres and energy centres, and their RPC-B15 and RPC-B50 versions have a power of 25, 50, 75 or 100 kvar, as well as 37.5 kvar, and contactors with pre-insertion resistors. The RCM racks go into G6E and G8E cabinets, without reactors (B15, B35, B50) or in the anti-resonance versions AAR/100, AAR/600, AAR/6, AAR/138, AAR/D20. All RCL racks for G9E cabinets have blocking reactors AAR/138 or AAR/D20. The self-healing MKP capacitors with a pressure protection device and a discharge resistor are impregnated with vegetable oil free of PCB and connected in delta, and they withstand 1.1 Un overvoltage and 1.3 In current, with a capacitance tolerance of −5/+10 %. The reactors of 189 Hz (p = 7 %) or 138 Hz (p = 14 %) have a temperature sensor that switches the step off on overheating. The power circuits are protected by NH-00 gG fuses of 100 kA and switched by AC6-b contactors, and the auxiliary circuits are supplied from 230 V AC.

How to choose

The version is chosen by the current THD in the network. Without a reactor the B15 works up to 15 %, the B35 up to 25 %, the B50 up to 35 %, and the anti-resonance AAR versions withstand up to 100 %. As the permissible harmonic level grows, so does the capacitor voltage, from 415/450 V in the B15 and 450/500 V in the B35 to 500/550 V in the B50, AAR/100 and AAR/600, and 550/600 V in the AAR/6, AAR/138 and AAR/D20 versions. The steps are controlled by a BMR 4, BMR 6 or HPR controller, and for targeted sinking of the 5th harmonic there is the passive FAM05 filter for 245 Hz.

Request a price and lead time

RPC / RCM / RCL capacitor racks (withdrawable modules) for 0.4 kV reactive power compensation switchboards. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

Does a cabinet with RCM capacitor racks need ventilation?

Yes, the rack is IP00 and has no fan of its own, so ventilation and the enclosure are provided by the panel builder.

What losses does the reactor of an anti-resonance rack have?

A 189 Hz reactor has losses of 6 W/kvar and a 138 Hz reactor 6.5 W/kvar, and they are included in the thermal calculation of the cabinet.

What are the dimensions of the RPC module for a 19-inch cabinet?

The dimensions given for the RPC module are 440 × 340 × 490 × 270 mm.

Which standards and directives do the RCM and RCL racks comply with?

The racks comply with IEC/EN 60831-1/2, EN 61921 and directives 2014/35/EC and 2014/30/EC, and 100 % of them undergo inspection and insulation tests.

Similar products

Low-voltage equipment

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.