Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

LOW-VOLTAGE EQUIPMENT

iR-AM06-VI — analogue input/output module (voltage/current)

4 AI + 2 AO · 16-bit ADC, 12-bit DAC · accuracy ±0.2% FS · 0…+55 °C

The iR-AM06-VI is a compact iR-series module that combines 4 analogue inputs and 2 analogue outputs for voltage and current signals in a single housing. The inputs accept 0…10 V, ±10 V, 0…5 V, ±5 V, 0…20 mA and 4…20 mA signals from temperature, pressure, level, flow and position sensors. Conversion is carried out at 16-bit resolution, with a sampling time of approximately 2 ms per channel. The outputs deliver 0…10 V, ±10 V, 0…20 mA or 4…20 mA at 12-bit resolution to drive variable-frequency drives, valves and positioners. Output settling time is no more than 1 ms. Accuracy is ±0.2% FS on both inputs and outputs. Galvanic isolation between the channels and the logic reduces the effect of interference. The module mounts on a DIN rail and is rated IP20. It connects to PLC, HMI and SCADA systems through the series communication modules, or it can run as part of a CODESYS controller. Typical applications are industrial automation, process control and the food industry.

Analogue inputs
4 channels
Analogue outputs
2 channels
Input voltage ranges
0…10 V, ±10 V, 0…5 V, ±5 V
Input current ranges
0…20 mA, 4…20 mA

Technical specifications

Analogue inputs4 channels
Analogue outputs2 channels
Input voltage ranges0…10 V, ±10 V, 0…5 V, ±5 V
Input current ranges0…20 mA, 4…20 mA
Input resolution16 bit
Input accuracy±0.2% FS
Input sampling time~2 ms/channel
Output voltage ranges0…10 V, ±10 V
Output current ranges0…20 mA, 4…20 mA
Output resolution12 bit
Output accuracy±0.2% FS
Voltage output load≥ 2 kΩ
Current output load≤ 500 Ω
Output settling time≤ 1 ms
Galvanic isolationyes
Current consumption~70 mA
Operating temperature0…+55 °C
Degree of protectionIP20
MountingDIN rail
Dimensions30 × 109 × 81 mm
Weight~130 g

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

Choose the iR-AM06-VI when a single point needs both analogue measurement and analogue output: 4 inputs and 2 outputs. If only voltage/current inputs are required, the iR-AI04-VI is suitable. For temperature sensors, use the iR-AI04-TR.

Similar products

Low-voltage equipment

Request a price and lead time

iR-AM06-VI — analogue input/output module (voltage/current). We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.