Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

LOW-VOLTAGE EQUIPMENT

SPREPOWER LV low-voltage switchgear assemblies up to 690 V, 6300 A

SPREPOWER LV is low-voltage switchgear for operating voltages up to 690 V AC with busbars up to 6300 A and a withstand current Icw up to 120 kA. The panels are type-tested to IEC 61439. They are installed as main boards and auxiliary boards of power plants and substations, and as MCCs of industrial plants.

Voltage
up to 690 V AC
Main busbar current
up to 6300 A (rear, top or bottom)
Withstand current Icw
up to 120 kA
Separation
form 1–4b

Technical specifications

Voltageup to 690 V AC
Main busbar currentup to 6300 A (rear, top or bottom)
Withstand current Icwup to 120 kA
Separationform 1–4b
Degree of protectionIP30 / IP31 / IP54
StandardIEC 61439, type-tested switchgear assembly
Systemsair circuit breakers (ACB), fuse switch disconnectors up to 630 A, plug-in modules, withdrawable modules
Dimensionspanel width 400–1200 mm, height 2000/2200 mm, depth 600/800 mm
Certificationparticipant of the Panelbuilder programme for EMEA panel builders

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The boards are assembled from a modular system of blocks, so expansion does not require rebuilding the existing sections. The busbars with a rated current up to 6300 A are placed at the rear, top or bottom, depending on where the cables or busways enter. Internal separation is made to forms 1–4b. The degree of protection IP30, IP31 or IP54 is chosen according to the room conditions, and the enclosure colour is RAL 7035. The panels are installed against a wall, back to back or standing alone. The panel width is 400–1200 mm, the height 2000 or 2200 mm and the depth 600 or 800 mm. The design can be fixed or fully withdrawable. The scope of supply includes design, final assembly, factory tests, installation and commissioning. The assembly quality is confirmed by participation in the Panelbuilder programme for EMEA panel builders with regular audits. Within the line, DC boards, reactive power compensation units, ATS devices, transformer substations and transformer busbar connections are also made.

How to choose

The current level is set by the main busbars, and outgoing lines up to 630 A are built on the fuse switch disconnector system. Air circuit breakers are taken for incomers and high-power outgoing lines, and plug-in modules for motor starters and compact circuit breakers. For motor starters and power supply there are also withdrawable modules. If the board is in a dusty or damp room, change from IP30 to IP54. Non-standard schemes, for example ATS, are assembled as a special version.

Request a price and lead time

SPREPOWER LV low-voltage switchgear assemblies up to 690 V, 6300 A. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What is the maximum voltage of SPREPOWER LV?

The rated operating voltage reaches 690 V AC. The busbars are rated for a current up to 6300 A.

What short-circuit current does the switchgear assembly withstand?

The rated short-time withstand current Icw is up to 120 kA. The boards are type-tested to IEC 61439.

What are the dimensions of SPREPOWER LV panels?

The panel width is 400–1200 mm, the height 2000 or 2200 mm and the depth 600 or 800 mm.

Which degrees of protection and enclosure colour are available?

IP30, IP31 and IP54 are available, and the enclosure colour is RAL 7035.

For which outgoing lines is the fuse switch disconnector system suitable?

For outgoing lines up to 630 A. Incomers and higher-power outgoing lines are built with air circuit breakers.

Similar products

Low-voltage equipment

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.