Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

LOW-VOLTAGE EQUIPMENT

PBD / PBS / E14, E18 LV fuse bases and NH fuse links up to 630 A

PBD, PBS and modular E14/E18 fuse bases hold the fuse link and connect it into the circuit of LV switchgear for currents up to 630 A and voltages up to 690 V. The classic bases are used in cable and utility cabinets, industrial and power switchboards and LV reactive power compensation banks.

PBD (classic)
single-pole, NH00/1/2/3, up to 630 A, 690 V; for a mounting panel; M12 clamp and V-shaped clamp, cable up to 240 mm²
PBS (busbar-type)
three-pole, for busbars; PBS 00, 00/100 mm, 2, 3; PBS 3: 630 A, 690 V, Ui 1000 V, 100 kA, 60 W, IP20
E14 / E18
modular; 400 V AC / 250 V DC; Uimp 6 kV; 50 kA AC / 8 kA DC; V0, GWT 960 °C, CTI 600; IP20
NH fuse links
sizes 000–3, 2–630 A, 500 V AC, 120 kA

Technical specifications

PBD (classic)single-pole, NH00/1/2/3, up to 630 A, 690 V; for a mounting panel; M12 clamp and V-shaped clamp, cable up to 240 mm²
PBS (busbar-type)three-pole, for busbars; PBS 00, 00/100 mm, 2, 3; PBS 3: 630 A, 690 V, Ui 1000 V, 100 kA, 60 W, IP20
E14 / E18modular; 400 V AC / 250 V DC; Uimp 6 kV; 50 kA AC / 8 kA DC; V0, GWT 960 °C, CTI 600; IP20
NH fuse linkssizes 000–3, 2–630 A, 500 V AC, 120 kA
Conditions−25…+55 °C, up to 2000 m; outdoors in an enclosure of at least IP34
StandardsPN-EN 60269-1, PN-HD 60269-2

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The single-pole PBD bases are fixed to a mounting panel, with copper jaw contacts screwed to a body of non-flammable plastic. In sizes 00, 1 and 2 the contacts are tinned (silver on special order), and in size 3 silver is standard. The PBD 3 is rated for 630 A and 690 V, a cable of up to 240 mm² is led under an M12 clamp or a V-shaped bracket, and busbars can be connected as well. The three-pole busbar-type PBS bases sit directly on the busbars and free up a good deal of space in the switchboard compared with panel-mounted bases, and the range includes PBS 00, PBS 00/100 mm, PBS 2 and PBS 3. For the PBS 3 the thermal current is 630 A, Ui is 1000 V, 50–60 Hz, power dissipation is 60 W, peak withstand current is 100 kA, and the protection is IP20 without fuse links and with fuse links under the covers. The modular E14 and E18 for cylindrical fuse links are mounted on a DIN rail, the V0 class plastic withstands a glow wire of 960 °C at CTI 600, the separators are stainless steel, and the tightening torque is 2.0/2.5 N·m. The bases comply with PN-EN 60269-1 and PN-HD 60269-2.

How to choose

The base type determines the mounting method. PBD is taken for a panel and cable, PBS for busbars, and E14/E18 for a DIN rail. NH fuse links are selected by base size (000–3) and by current from 2 to 630 A, with a voltage of 500 V AC and a breaking capacity of 120 kA. To switch a line under load, an RBK pro fuse switch disconnector for 125–630 A is installed instead of a base.

Request a price and lead time

PBD / PBS / E14, E18 LV fuse bases and NH fuse links up to 630 A. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

Does the current of the PBS 3 base need to be derated in a hot cabinet?

Yes, at +41…+45 °C the current is reduced by 5 %, and at +46…+55 °C by 10 %, so in a tight cabinet without ventilation the rating is taken with a margin.

What cable cross-section is the PBD 3 base designed for?

Up to 240 mm² through an M12 screw clamp or a V-shaped bracket. Busbars can be connected instead of a cable.

Are the modular E14 and E18 bases suitable for DC circuits?

Yes, the operating voltage is 400 V AC or 250 V DC, with Uimp of 6 kV. The rated short-circuit current is 50 kA on AC and 8 kA on DC.

In what conditions can PBD and PBS fuse bases be installed?

In rooms free of dust and aggressive gases at −25…+55 °C and at altitudes up to 2000 m. Outdoors only in an enclosure of at least IP34.

Similar products

Low-voltage equipment

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.