Ukrainian Components WarehouseA USK project
UKRSKINDUSTRIAL COMPONENTS

LOW-VOLTAGE EQUIPMENT

МІК-121Т — universal microprocessor PID controller with extended functions

measurement accuracy ≤ 0.2 % · measuring range 0–2500 °C · supply 24–230 V AC/DC · 2 AI / 1 AO / 2 DI / 4 DO

The МІК-121Т is a universal microprocessor controller for automatic regulation of temperature, pressure, level, humidity and flow. It accepts sensor signals on two universal analogue inputs (current, voltage, thermocouples, resistance thermometers), applies digital filtering and scaling, and generates a control signal for the actuator according to the selected algorithm. Analogue, pulse and PWM PID control are available, together with on/off, three-position, cascade, ratio and corrected PID control. Measurement accuracy is ≤ 0.2 % and measurement time is no more than 0.1 s. The unit provides one analogue output, four discrete outputs (transistor or relay), two discrete inputs, a four-digit display, non-volatile EEPROM memory and an RS-485 interface with Modbus RTU. Inputs, outputs and the supply circuit are galvanically isolated at not less than 500 V. Typical applications include power generation, metallurgy, and the chemical and food industries.

Analogue inputs
2
Discrete inputs
2
Analogue outputs
1
Discrete outputs
4 (transistor or relay)

Technical specifications

Analogue inputs2
Discrete inputs2
Analogue outputs1
Discrete outputs4 (transistor or relay)
Input signal typescurrent, voltage, thermocouples, resistance thermometers
Measuring range0–2500 °C
Measurement accuracy≤ 0.2 %
Measurement time≤ 0.1 s
Control modesPID (analogue, pulse, PWM), on/off, three-position, cascade, ratio, corrected PID
Displaydigital, four-digit
Non-volatile memoryEEPROM
Interface / protocolRS-485 / Modbus RTU
Galvanic isolation voltagenot less than 500 V
Supply voltage24–230 V AC/DC
Power consumption (AC)3.6–8.5 VA
Current consumption (DC)150–250 mA
Max. discrete output voltage40; 250 V
Max. discrete output current8; 100 mA/A
Mountingpanel, DIN rail, wall
Degree of protectionIP30, IP65
Case versionsМІК-121: 96х96х135 mm, panel; МІК-121Н: 110х160х58 mm, DIN rail; МІК-21: 145х120х80 mm, wall
Dimensions96х96х135 mm; 110х160х58 mm; 145х120х80 mm
Weightmax. 0.35 kg
Special versionfront panel with Ukrainian lettering
StandardsДСТУ EN 60529:2014, ДСТУ 2858-94, ДСТУ 2837-94, ГОСТ3044-94, DIN IEC 584-1, DIN EN 44070

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

Choose the version by mounting method: МІК-121 for panel mounting (96х96х135 mm case), МІК-121Н for DIN-rail mounting (110х160х58 mm) and МІК-21 for wall mounting (145х120х80 mm). Also specify the supply voltage (24 V DC or 230 V AC), output type (transistor or relay), input signal type and degree of protection (IP30 or IP65). A front panel with Ukrainian lettering is available.

Similar products

Low-voltage equipment

Request a price and lead time

МІК-121Т — universal microprocessor PID controller with extended functions. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.