ПТС-164, ПТС-164МІ — process alarm signalling device for up to 64 channels

up to 64 channels · 24 V DC supply · relay contacts 8 A / 220 V · RS-485, Modbus RTU (ПТС-164МІ)

The ПТС-164 is a modular process alarm signalling device. It alerts operating staff when process parameters move beyond their set limits and provides both a common alarm and channel-by-channel indication. A system is made up of a ПТС-25 master block and ПТС-85 remote blocks and covers from 1 to 64 channels. Indication can be steady or flashing, and events are stored in memory until acknowledged. The delay time is adjustable from 1.5 to 35 s. The outputs use changeover relay contacts rated for load currents up to 8 A and switched voltages up to 220 V. The device runs on a 24 V DC supply. The ПТС-164МІ version adds the ПТС-32МІ module with an RS-485 interface and the Modbus RTU protocol. It supports up to 32 devices per segment, line lengths up to 1200 m and a speed of 62.5 kbit/s. All blocks mount on a DIN rail. Typical applications are local and integrated industrial automation systems and process or emergency alarm circuits.

Number of channels
1…64
Supply voltage
24 V DC
Output type
changeover relay contacts
Max. load current
8 A

Technical specifications

Number of channels1…64
Supply voltage24 V DC
Output typechangeover relay contacts
Max. load current8 A
Max. switched voltage220 V
Input resistance100 Ω
Delay time1.5…35 s
Flashing parameter F10.06…0.25 s
Flashing parameter F20.69…2.55 s
Max. consumption, ПТС-2550 mA
Max. consumption, ПТС-85170 mA
Max. consumption, ПТС-32МІ50 mA
Max. consumption, ПТС-8ПС45 mA
Max. output voltage, ПТС-8524 V
Max. output consumption, ПТС-8550 mA
Max. total consumption, ПТС-855 A
Interface / protocol (ПТС-164МІ)RS-485 / Modbus RTU
Devices per RS-485 segment32
Max. RS-485 line length1200 m
Data rate62.5 kbit/s
Network address range0…255
MountingDIN rail 35×7.5 EN50022
Degree of protectionIP00
Climatic versionУХЛ 4.2
Relative humidity30…80 % non-condensing (at +35 °C)
Atmospheric pressure84…106.7 kPa
Vibration60 Hz, amplitude 0.1 mm
Insulation test voltage500 V, 50 Hz
Insulation resistance20 MΩ
MTBF100 000 hours
Restoration time2 hours
Service life10 years
Storage life1 year
Dimensions, ПТС-2586×141×45 mm
Dimensions, ПТС-8586×180×45 mm
Dimensions, ПТС-32МІ86×180×50 mm
Dimensions, ПТС-8ПС86×40×45 mm
Weight, ПТС-250.18 kg
Weight, ПТС-850.25 kg
Weight, ПТС-32МІ0.2 kg
Weight, ПТС-8ПС0.045 kg
StandardsГОСТ15150-69, ГОСТ 14254-96, ГОСТ 26828, ГОСТ 12971, ГОСТ 23170, EN50022

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

How to choose

Choose the ПТС-164 for stand-alone signalling. The ПТС-164МІ with an RS-485 interface (Modbus RTU) is needed when the device must connect to a control network. Select the channel count to match the number of monitored signals: 1, 8, 16, 24, 32, 40, 48, 56 or 64. For priority signalling, the system can be extended with the ПТС-8ПС block.

Similar products

Low-voltage equipment

Request a price and lead time

ПТС-164, ПТС-164МІ — process alarm signalling device for up to 64 channels. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.