RIO-DIO16 — combined discrete input/output module
Country: Ukraine · Model: RIO-DIO16
8 DI + 8 DO · RS-485, Modbus RTU · 24 V DC / 230 V AC supply · -40 °C to +70 °C
The RIO-DIO16 is a remote I/O module that combines 8 discrete inputs and 8 discrete outputs in a single housing. The inputs accept =24 V signals from n-p-n type sensors: logic 0 corresponds to 0–7 V, logic 1 to 18–30 V, with input current up to 10 mA. Outputs are either NPN transistor (up to 40 V, up to 100 mA) or mechanical relay (up to 230 V, up to 5 A), allowing actuators to be driven directly. The module exchanges data with a PLC, panel controller or PC over RS-485 using the Modbus RTU protocol. It is powered from 24 V DC (130 mA) or 230 V AC (3.5 VA), and galvanic isolation is rated at 500 V. The 117х23х129 mm housing, weighing 0.18 kg and rated IP20, mounts on a DIN rail and operates from -40 °C to +70 °C. Typical use is on industrial automation sites for acquiring discrete sensor states and switching loads.
- Number of discrete inputs
- 8
- Input signal type
- n-p-n
- Input voltage
- =24 V
- Logic 0 level
- 0–7 V
Technical specifications
| Number of discrete inputs | 8 |
|---|---|
| Input signal type | n-p-n |
| Input voltage | =24 V |
| Logic 0 level | 0–7 V |
| Logic 1 level | 18–30 V |
| Input current | up to 10 mA |
| Number of discrete outputs | 8 |
| Output type | NPN transistor, mechanical relay |
| Transistor output: voltage / current | up to 40 V / up to 100 mA |
| Relay output: voltage / current | up to 230 V / up to 5 A |
| Interface | RS-485 |
| Protocol | Modbus RTU |
| Supply voltage DC | 24 V |
| Supply voltage AC | 230 V |
| Consumption, DC supply | 130 mA |
| Consumption, AC supply | 3.5 VA |
| Galvanic isolation voltage | 500 V |
| Mounting | DIN rail |
| Ingress protection | IP20 |
| Operating temperature | -40 °C to +70 °C |
| Dimensions | 117х23х129 mm |
| Weight | 0.18 kg |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
How to choose
NPN transistor outputs (up to 40 V, 100 mA) suit low-current circuits and frequent switching. Relay outputs (up to 230 V, 5 A) are intended for switching mains loads. Choose the supply to match the available source: 24 V DC or 230 V AC. If a USB interface is needed, consider RIO-5N-DI8-DO8. For 4 inputs and 4 outputs, a 20 kHz pulse frequency or a solid state relay option, consider RIO-mini DI4DO4.
Similar products
Request a price and lead time
RIO-DIO16 — combined discrete input/output module. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.