RTL / RTLs / RTE / RTEa — transformer LV distribution boards up to 690 V, 2 000 A
Country: Poland · Model: RTL / RTLs / RTE / RTEa
RTL, RTLs, RTE and RTEa are a range of low-voltage distribution boards for transformer substations for voltage up to 690 V and rated current up to 2 000 A. The boards are intended for container and indoor substations and for LV switchgear at industrial, commercial and municipal facilities.
- Voltage
- Un 230/400 V; Ui 690 V; Uimp 8 kV
- Main busbar current
- up to 2 000 A
- Outgoing feeder current
- 160 / 250 / 400 / 630 A
- 1 s / peak current
- 50 kA / 105 kA
Technical specifications
| Voltage | Un 230/400 V; Ui 690 V; Uimp 8 kV |
|---|---|
| Main busbar current | up to 2 000 A |
| Outgoing feeder current | 160 / 250 / 400 / 630 A |
| 1 s / peak current | 50 kA / 105 kA |
| Protection rating | IP30 at the front (with devices of the board manufacturer, Jean Müller); IP20 (OEZ, Efen); IP40 other compartments |
| IK | IK 40 (per catalogue) |
| RTL dimensions | height 1 850 mm, width 600–2 500 mm, depth 250/400 mm |
| Frame | galvanized 50×25 profile, 25 mm pitch; Cu busbars with 185 mm pitch |
| Networks | TN-S, TN-C, TN-C-S, TT, IT |
| Standards | PN-EN 60439 (certificate 1025/NBR/2010), PN-EN 60529 |
Specifications are taken from the manufacturer’s technical documentation. Updated .
Description
The frame is assembled from thin-walled perforated galvanized profiles of 50 × 25 mm with a perforation pitch of 25 mm, and the front doors are made of 1.5 mm painted sheet (RAL 7032). The board height is 1 850 mm, width 600–2 500 mm, depth 250 mm for busbars up to 1 250 A and 400 mm above that current. All busbars are copper, the main phase busbars are arranged vertically with a centre distance of 185 mm, and strip-type devices are mounted directly on them. The main device can be an in-line switch-disconnector up to 1 250 A (RWS 1250), its fused version (ARS), a rotary switch up to 2 000 A, an MCCB for 630–1 600 A or an ACB for 1 000–2 000 A, and instead of one device of sizes 1–3 two of size 00 can be fitted. For the RTL the rated voltage Un is 230/400 V, Ui 690 V, Uimp 8 kV (1.2/50 µs), outgoing feeder current 160, 250, 400 or 630 A, 1 s current 50 kA, peak 105 kA. The protection rating is IP30 at the front, IP20 with OEZ and Efen devices and IP40 for the other compartments. Compliance with PN-EN 60439 and PN-EN 60529, certificate No. 1025/NBR/2010. Operating conditions are free of dust and aggressive gases, from −25 to +40 °C.
How to choose
The RTL has small dimensions and permits current and energy measurement in outgoing circuits, cable connection without crimping lugs, and operation in TN-S, TN-C, TN-C-S, TT and IT networks. The RTLs additionally has automatic transfer switching, cable entry from below and above, the ZUMiS remote monitoring system and fuse-link blow monitoring.
Request a price and lead time
RTL / RTLs / RTE / RTEa — transformer LV distribution boards up to 690 V, 2 000 A. We reply within one business day.
Or email office@usk.ua or call +38 (044) 339-50-20.
FAQ
What voltage and current are RTL boards rated for?
Rated voltage Un 230/400 V, insulation Ui 690 V, main busbar current up to 2 000 A, outgoing feeders 160, 250, 400 and 630 A.
In which networks can RTL be used?
In TN-S, TN-C, TN-C-S, TT and IT networks.
Which main device can be installed in the board?
An in-line switch-disconnector up to 1 250 A, its fused version, a rotary switch up to 2 000 A, an MCCB of 630–1 600 A or an ACB of 1 000–2 000 A.
What is the board short-circuit withstand?
The 1 s current is 50 kA, the peak current 105 kA.
Similar products
REQUEST
Need a price, lead time or replacement?
Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.