RTL / RTLs / RTE / RTEa — transformer LV distribution boards up to 690 V, 2 000 A

RTL, RTLs, RTE and RTEa are a range of low-voltage distribution boards for transformer substations for voltage up to 690 V and rated current up to 2 000 A. The boards are intended for container and indoor substations and for LV switchgear at industrial, commercial and municipal facilities.

Voltage
Un 230/400 V; Ui 690 V; Uimp 8 kV
Main busbar current
up to 2 000 A
Outgoing feeder current
160 / 250 / 400 / 630 A
1 s / peak current
50 kA / 105 kA

Technical specifications

VoltageUn 230/400 V; Ui 690 V; Uimp 8 kV
Main busbar currentup to 2 000 A
Outgoing feeder current160 / 250 / 400 / 630 A
1 s / peak current50 kA / 105 kA
Protection ratingIP30 at the front (with devices of the board manufacturer, Jean Müller); IP20 (OEZ, Efen); IP40 other compartments
IKIK 40 (per catalogue)
RTL dimensionsheight 1 850 mm, width 600–2 500 mm, depth 250/400 mm
Framegalvanized 50×25 profile, 25 mm pitch; Cu busbars with 185 mm pitch
NetworksTN-S, TN-C, TN-C-S, TT, IT
StandardsPN-EN 60439 (certificate 1025/NBR/2010), PN-EN 60529

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The frame is assembled from thin-walled perforated galvanized profiles of 50 × 25 mm with a perforation pitch of 25 mm, and the front doors are made of 1.5 mm painted sheet (RAL 7032). The board height is 1 850 mm, width 600–2 500 mm, depth 250 mm for busbars up to 1 250 A and 400 mm above that current. All busbars are copper, the main phase busbars are arranged vertically with a centre distance of 185 mm, and strip-type devices are mounted directly on them. The main device can be an in-line switch-disconnector up to 1 250 A (RWS 1250), its fused version (ARS), a rotary switch up to 2 000 A, an MCCB for 630–1 600 A or an ACB for 1 000–2 000 A, and instead of one device of sizes 1–3 two of size 00 can be fitted. For the RTL the rated voltage Un is 230/400 V, Ui 690 V, Uimp 8 kV (1.2/50 µs), outgoing feeder current 160, 250, 400 or 630 A, 1 s current 50 kA, peak 105 kA. The protection rating is IP30 at the front, IP20 with OEZ and Efen devices and IP40 for the other compartments. Compliance with PN-EN 60439 and PN-EN 60529, certificate No. 1025/NBR/2010. Operating conditions are free of dust and aggressive gases, from −25 to +40 °C.

How to choose

The RTL has small dimensions and permits current and energy measurement in outgoing circuits, cable connection without crimping lugs, and operation in TN-S, TN-C, TN-C-S, TT and IT networks. The RTLs additionally has automatic transfer switching, cable entry from below and above, the ZUMiS remote monitoring system and fuse-link blow monitoring.

Request a price and lead time

RTL / RTLs / RTE / RTEa — transformer LV distribution boards up to 690 V, 2 000 A. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What voltage and current are RTL boards rated for?

Rated voltage Un 230/400 V, insulation Ui 690 V, main busbar current up to 2 000 A, outgoing feeders 160, 250, 400 and 630 A.

In which networks can RTL be used?

In TN-S, TN-C, TN-C-S, TT and IT networks.

Which main device can be installed in the board?

An in-line switch-disconnector up to 1 250 A, its fused version, a rotary switch up to 2 000 A, an MCCB of 630–1 600 A or an ACB of 1 000–2 000 A.

What is the board short-circuit withstand?

The 1 s current is 50 kA, the peak current 105 kA.

Similar products

Low-voltage equipment

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.