FYX terminals, terminal blocks and wire connectors

FYX is a system of terminal products for distribution boards, boxes and electrical installations. It includes insulated N and PE bars with 5–28 sockets of 6 mm², RE screw blocks for 2.5–35 mm², TCD DIN-rail terminals for 1.5–35 mm² and quick wire connectors.

N/PE bars
5 … 28 × 6 mm² (+ 4 × 16 mm²)
RE terminal blocks
12 poles, 2.5 … 35 mm² (2.5 mm²: 18 A, 450 V)
TCD DIN-rail terminals
1.5 … 35 mm², phase / N / PE
Other
CLE quick terminals with 2–5 inputs (4 mm² solid / 2.5 mm² flexible), CLC connectors 0.5–10 mm², CLG IP67 connectors, REV feed-through 2.5–10 mm²

Technical specifications

N/PE bars5 … 28 × 6 mm² (+ 4 × 16 mm²)
RE terminal blocks12 poles, 2.5 … 35 mm² (2.5 mm²: 18 A, 450 V)
TCD DIN-rail terminals1.5 … 35 mm², phase / N / PE
OtherCLE quick terminals with 2–5 inputs (4 mm² solid / 2.5 mm² flexible), CLC connectors 0.5–10 mm², CLG IP67 connectors, REV feed-through 2.5–10 mm²

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

Insulated blocks are installed in the standard sockets of Metalbox, Vera and Arelos boards and Mecabox boxes by pressing them in until they stop. These are the 105N/105PE for 5×6 mm², 113N/113PE for 13×6 mm² and 4×16 mm², 180N/180PE for 18×6 mm² and 6×16 mm², 128N/128PE for 28×6 mm² and 6×16 mm², and the combined 113PE/N with 13 PE outputs and 13 N outputs. Neutral is blue, earth is green. Strips 108P and 112P have 8 or 12 clamps for wire up to 6 mm² and 2 clamps up to 16 mm², and strips 212N and 212TT on a thermoplastic base have 12×6 mm² and 2×16 mm². The 12-pole RE screw blocks (10 pcs., 450 V) for cross-sections of 2.5, 4, 6, 10, 16, 25 and 35 mm² have currents of 18, 24, 41, 57, 80, 100 and 125 A, and tightening torques of 0.4, 0.4, 0.5, 0.8, 1.2, 2 and 2 N·m.

How to choose

Choose the type by location and the number of conductors. For neutral and earth in boards take the 105–128 bars, for branches in boxes the CLE quick terminals with 2, 3 or 5 inputs with 4 mm² solid or 2.5 mm² flexible wire, and for joining wires the CLC for 0.5–2.5, 0.5–6 and 0.5–10 mm². The sealed CLG for 3×1.5 mm² is rated IP67, and TCD terminals for 1.5–35 mm² come in phase, neutral and earth colours. The transparent feed-through REV have 2×2.5, 2×4, 2×6 and 2×10 mm².

Request a price and lead time

FYX terminals, terminal blocks and wire connectors. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

How many poles do RE blocks have and what current are they rated for?

The blocks have 12 poles and 450 V, and the current ranges from 18 A for 2.5 mm² to 125 A for 35 mm².

Which insulated N and PE bars are part of FYX?

105N/105PE, 113N/113PE, 180N/180PE, 128N/128PE and the combined 113PE/N block.

What tightening torque do RE blocks have?

From 0.4 N·m for 2.5 and 4 mm² to 2 N·m for 25 and 35 mm².

Into which boards are insulated N and PE blocks installed?

Into the standard sockets of Metalbox, Vera and Arelos boards and Mecabox boxes, by pressing in until they stop.

What is the protection rating of the CLG connector?

IP67, cross-section 3×1.5 mm², so it is used where a sealed joint is needed.

Similar products

Low-voltage equipment

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.