POWER TRANSFORMERS

TC_ / TC_CV current transformers with built-in measuring converter (20 mA / 4–20 mA output)

TC_ and TC_CV combine a feed-through current transformer and a measuring converter and deliver an analog DC signal of 20 mA or 4–20 mA instead of an AC 1 or 5 A. The signal goes straight to the input of a PLC, SCADA controller or recorder, so the current of motors, pumps and fans is monitored without a separate converter.

TC_
TC40 (busbar 40×10, cable Ø32), TC60 (60×10, Ø50), TC80 (80×30, Ø65); output 20 mA; class 0.5; max. burden 600 Ω
TC_CV
TC20CV (20×5, Ø16), TC30CV (30×10, Ø22), TC40CV (40×10, Ø30); output 4–20 mA; class 1; switchable ratio (multi-range)
TC_CV supply
10–40 V DC
TC_CV working range
10–120 %

Technical specifications

TC_TC40 (busbar 40×10, cable Ø32), TC60 (60×10, Ø50), TC80 (80×30, Ø65); output 20 mA; class 0.5; max. burden 600 Ω
TC_CVTC20CV (20×5, Ø16), TC30CV (30×10, Ø22), TC40CV (40×10, Ø30); output 4–20 mA; class 1; switchable ratio (multi-range)
TC_CV supply10–40 V DC
TC_CV working range10–120 %
Frequency50–60 Hz
Operating temperature−5…+40 °C
Insulation classE (B, 130 °C — on request)

Replacement for

no direct analogue; closest — T-0.66 with E842, E854 measuring current transducers

selected by purpose and main parameters, please confirm with the manager

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

TC40, TC60 and TC80 have windows for 40×10, 60×10 and 80×30 mm busbars or Ø32, Ø50 and Ø65 mm cable, a 20 mA output, class 0.5 and a maximum load resistance of 600 Ω. The TC_CV in a plastic housing have a primary current switch, so one device covers several ratings. TC20CV is designed for a 20×5 mm busbar or Ø16 mm cable, TC30CV for 30×10 mm or Ø22 mm, and TC40CV for 40×10 mm or Ø30 mm. The output is 4–20 mA, class 1, the working range is 10–120 % of the rating, and the auxiliary supply is 10–40 V DC. Frequency 50–60 Hz, operating temperature −5…+40 °C, insulation class E (B, 130 °C on request). A CE declaration has been issued for TC_CV.

How to choose

First choose the window to suit the busbar or cable. If the line current is known and does not change, TC_ with a 20 mA output will do, and when the rating may change, take TC_CV with the switch and a 4–20 mA output. TC_ has class 0.5 and TC_CV has class 1, so for more accurate monitoring choose TC_. For an ordinary 1 or 5 A secondary output, look at TUC_ or TU_PS.

Request a price and lead time

TC_ / TC_CV current transformers with built-in measuring converter (20 mA / 4–20 mA output). We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

How does TC_ differ from TC_CV?

TC_ gives 20 mA and class 0.5 with a fixed rating. TC_CV has a primary current switch, a 4–20 mA output, class 1 and a 10–40 V DC supply.

What burden can be connected to the TC_ output?

The maximum load resistance is 600 Ω at a 20 mA DC output.

What working range does TC_CV have?

10–120 % of the rating, and the rating itself is set with the switch.

What are the operating conditions and insulation class?

Frequency 50–60 Hz, temperature −5…+40 °C, insulation class E, class B (130 °C) on request.

Similar products

Power transformers

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.