DYN11 dry-type low-voltage isolating transformers 7–2000 kVA

Dry-type isolating transformer for low voltage, 7–2000 kVA, with Dyn11 connection and an electrostatic screen. Rated voltage is 400/400 V at 50 Hz. It sits in front of UPS units and other sensitive equipment in data centres, medical facilities and industrial sites.

Power
K4: 10–1000 kVA (Cu), 40–2000 kVA (Al); K13 and K20 up to 800/1600 kVA
Connection
delta/star Dyn11
K-factor
4, 13, 20
Voltage
400/400 V, 50 Hz

Technical specifications

PowerK4: 10–1000 kVA (Cu), 40–2000 kVA (Al); K13 and K20 up to 800/1600 kVA
Connectiondelta/star Dyn11
K-factor4, 13, 20
Voltage400/400 V, 50 Hz
Windingscopper or aluminium
EnclosureIP00 or IP21
StandardsEN 60076 / IEC 61558

Replacement for

TSZI, TSZ 0.38/0.23 kV (dry low-voltage), OSM1-0.063…4 kVA (single-phase), OSO; K-factor — made to special order

selected by purpose and main parameters, please confirm with the manager

Replacement pages: ОСМ1-0,063, ОСМ1

Specifications are taken from the manufacturer’s technical documentation. Updated .

Description

The delta/star Dyn11 connection and the 400/400 V ratio give galvanic isolation without changing the voltage level. The electrostatic screen reduces the transfer of high-frequency noise from the mains into the load. Windings are made of copper or aluminium. For K-factor 4 the range is 10–1000 kVA with copper and 40–2000 kVA with aluminium, while the K13 and K20 versions go up to 800/1600 kVA. The enclosure is supplied in the IP00 or IP21 version.

How to choose

Start with the K-factor. The available values are 4, 13 and 20, and the more non-linear consumers the load contains, the higher the rating you need. Next comes the winding material. For K4, copper is offered up to 1000 kVA and aluminium up to 2000 kVA. IP00 suits a transformer that already stands inside a closed cabinet or chamber, while IP21 is for cases where protection against finger contact and vertically falling drops is required. If the network calls for a delta/zigzag connection, look at the DZN0 model, 7–2000 kVA, with class H insulation, 125 K temperature rise and M270 steel.

Request a price and lead time

DYN11 dry-type low-voltage isolating transformers 7–2000 kVA. We reply within one business day.

* — required fields

Or email office@usk.ua or call +38 (044) 339-50-20.

FAQ

What power ratings are available for the DYN11 transformer?

For K-factor 4 it is 10–1000 kVA with copper and 40–2000 kVA with aluminium windings. The K13 and K20 versions go up to 800/1600 kVA.

What does the Dyn11 connection mean and what is the output voltage?

The primary winding is delta-connected and the secondary is star-connected, with 11 denoting the vector group. The voltage is 400/400 V at 50 Hz, so the level stays unchanged.

Which K-factor should I choose for a UPS load?

The available K-factors are 4, 13 and 20. For a load with a large share of rectifiers take 13 or 20, while K4 fits when harmonics are low.

How do the IP00 and IP21 versions differ?

IP00 is the open version without an enclosure, while IP21 has an enclosure protecting against finger contact and vertical drips.

Which standards does the transformer meet and what is the screen for?

The design follows EN 60076 and IEC 61558. The electrostatic screen reduces the transfer of high-frequency noise between the mains and the load.

Similar products

Power transformers

REQUEST

Need a price, lead time or replacement?

Send us a request and we will confirm the configuration, lead time and delivery terms. We reply by email.

How we use your data

UKRSK, Ukrainian Components Warehouse, is a USK project. This form saves your email, request details, optional name and company, and attached files on the UKRSK server to process your enquiry. Files are not published in the catalogue. The form currently does not perform automated technical matching or send commercial quotations. To enquire about or delete your data, submit a request using this form and include your reference number. Do not attach passwords, payment details or unrelated confidential materials. Technical rate-limit records are stored separately; no advertising trackers are used.

To monitor page performance we collect LCP, INP and CLS measurements, language, screen category and a random measurement ID. These are stored on our hosting for up to 35 days; form contents, email, IP address and full URL are not recorded in this log. No cookies are used; Do Not Track and Global Privacy Control disable measurement.